Step 4: Wiring Information (continued)

IMporTanT!

additional Wiring notes:

For heat pumps with O and B both present, connect O wire to O terminal and B wire to C terminal (noTE:

This is typically for Trane Heat Pump products only.) Do not connect B wire to B terminal as it may

damage the 24VAC power system.

For LENNOX Pulse systems, please contact customer support or contact your HVAC professional for specific

information regarding installing the Z-Wave

®

Enabled Thermostat with your system.

Use 18- to 22-gauge thermostat wire.

Your Z-Wave® enabled thermostat must have a C wire (electrical power) and cannot operate from batteries

alone. Batteries are for back up only.

If you are unsure of how to connect your system, please call customer support for additional information or

contact an HVAC professional.

If you have 2 large wires (12 or 14 gauge or if it is bigger than paper clip wire) or know that your system

operates on line voltage, immediately stop, re-install your existing thermostat and contact customer support.
The Wayne-Dalton Z-Wave

®

Enabled thermostat operates on 24 Volts AC power only.

Jumper reference Guide

The number below corresponds to the bubble number above.

Jp5 --

Fan Control: a)

no Fan -No fan control even with switch on front of thermostat (RARE.)

(No jumper)

b)

ELECT - Fan is controlled from thermostat.

(Jumper on top 4 pins)

c)

GaS - Fan is controlled by furnace.

(Jumper on bottom 4 pins)

Jp3 --

Heat Pump Type: a)

oFF - No heat pump system present (Conventional HVAC System)

( No Jumper)

b)

on - Bypasses heat pump 1st stage and immediately triggers auxiliary heating.

(Eliminates time delay for effectively heating homes located in colder climates.)

(Jumper on top 4 pins)

c)

Heat pump - Normal heat pump setting to activate both stages.

(Jumper on bottom 4 pins)

Jp4 --

Power: a)

rC-rH Connected - For single transformer systems.

(Jumper on both pins)

b)

rC-rH Separate - For systems with a separate transformer for A/C and heat.

(No Jumper)

Jp1 --

Celsius/Fahrenheit: a)

°C - Thermostat will display in degrees Celsius.

(Jumper on both pins)

b)

°F - Thermostat will display in degrees Fahrenheit.

(No Jumper )

Jp2 --

Heat Pump Auxiliary Type: a) Fossil fuels - Natural gas, propane, or oil auxiliary system.

(Jumper on both pins)

b) Elect - Electric auxiliary system.

(No Jumper)

reset --

Reset Button - Always press the reset button after changing jumper settings.

noTE:

Unused jumpers may be stored by attaching them to a single pin.

reset

Installation

JP2

JP1

Continued Next Page

AUTO

ON

FAN

HEAT

COOL

SAVE

ENERGY

NORMAL

RESET

COOL

JP4

JP3

JP5