Waterpik Technologies pool/spa heater User Manual

Page 14

Advertising
background image

Page 12

d. Yellow Blower wire to terminal 8
e. White Blower wire to terminal 7

31. Reconnect the two white wires to the vent switch now

located just above the return header.

32. Reconnect the blower pressure switch tubing to the

blower housing.

33. Replace the EMI shield (metal plate) located over the

blower by reinstalling the two hex head screws.

34. Slide the upper right side panel back into the corner

posts on the right side of the heater. Push it down

until the tabs on the panel lock into the top of the

corner posts.

36. Install the flat return header side cover plate

(removed from the left side of the heater) on the right

side to cover the return header by replacing the four

philips head screws, one in each corner.

37. Slide the upper left side panel back into the corner

posts on the left side of the heater. Push it down until

the tabs on the panel lock into the top of the corner

posts.

38. Remove the button plug from the inlet/outlet side

cover plate.

39. Reinstall the inlet/outlet header side cover plate

located under the inlet/outlet header. It is held with

four philips head screws, one in each corner.

26. Route the wires that attach to the temperature sensor

along the copper siphon loop, back to the right side of

the heater. Reconnect the wires to the tabs on the

back of the control panel (marked as J4-1 and J4-2).

27. Use plastic wire ties to refasten the temperature

sensor and high limit switch wires to the copper

siphon loop. Bundle the wires near the control panel

and fasten them with a wire tie.

28. Replace the flue collector so that the blower mount is

in the same position as it was before the heat

exchanger reversal. Be sure that the bottom of the

flue collector lies flat on the top of the combustion

chamber and that it covers all of the heat exchanger

tubes. Replace the hex head screws to fasten the flue

collector to the combustion chamber.

29. Reassemble the blower and exhaust vent to the flue

collector. Be sure that the blower is seated properly

on the gasket and fasten it to the flue collector with

four hex head screws.

30. Reconnect the fan wires to the terminal strip as

follows: (Terminal numbers are shown on wires

connected to the bottom of the terminal strip)
a. Black Blower wire to terminal 11
b. Blue Blower wire to terminal 10
c. Red Blower wire to terminal 9

Figure 15. Typical Water Piping.

3-WAY

JANDY

CHANGEOVER

VALVE

3-WAY

JANDY

CHANGEOVER

VALVE