Waterpik Technologies pool/spa heater User Manual

Page 19

Advertising
background image

LX and LT Pool Heaters

Page 17

To adjust the pressure switch, proceed as follows (see

Figure 19).

The pool filter must be clean before making this

adjustment. The heater does not have to be firing.
1.

Set the heater control to the "OFF" position.

2.

Start the filter pump and confirm by means of an

voltmeter that the pressure switch closes (if the

switch fails to close, replace it with a switch which

has a lower minimum setting).

3.

Set the heater control to either 'Pool' or 'Spa'. Heater

should start.

4.

Pry out the top rubber dirt plug on the pressure

switch.

5.

Use a 7/32 inch Allen wrench to turn the adjustment

screw very slowly clockwise until the heater goes off.

6.

Slowly turn the pressure switch adjustment screw

counterclockwise one-quarter turn. The heater

should come back on.

7.

Check the adjustment by turning the filter pump OFF.

The heater fan will continue to run but the burners

should shut off immediately. If they do not, restart the

filter pump and repeat Steps 6 and 7. Check the

adjustment again.

8.

Return the pool temperature control to the desired

temperature.
It may be necessary to repeat these steps to get a

proper setting. The switch must be set so that the heater

will not fire unless the pump is running. If a proper setting

cannot be reached, contact the factory service department.

2J-5. Water Temperature Rise

The Laars LX and LT pool heaters have an internal

bypass which accommodates a wide range of water flow.

The bypass is easily adjustable to change the temperature

rise for optimum performance and length of heater life.

The bypass assures constant heat exchanger flow even

though flow through the filter system will vary depending

on how dirty the filter is.

For most installations, an external bypass valve is

not needed in the heater water piping. This is due to the

large size of the heater's internal bypass valve. If the pump

flow rate is known to significantly exceed 125 gpm

(7.9 l/s), an external bypass may be needed to assure

proper heater operation.

Water flow should be confirmed upon start-up of the

heater and in most servicing situations. If the flow is not

normal, corrections must be made to the pool system. Flow

is evaluated by determining the water temperature rise

through the heat exchanger.

Before checking the temperature rise, make sure that

the pool filter is clean. If necessary, clean all components

of the filter system. Temperature rise is measured in the

outlet of the far-right tubes when facing the inlet/outlet

water heater. To measure the temperature rise, turn off the

filter pump and remove the plastic plug to the right of, and

just below the level of the outlet water pipe. This is

mounted flush with the heater jacket (See Figure 20). With

the plug removed, install the special thread adapter and

"Pete’s" plug fitting and insert a pocket thermometer.

The internal bypass can be adjusted by means of a

screw on the right hand side of the header. To adjust the

temperature rise to within the ranges specified in table 8,

proceed as follows.

1.

If the piping system has an external bypass valve,

close it.

2.

Set the heater's control panel to the "Off" position.

3.

Start the filter pump.

4.

After three minutes, note and record the thermometer

reading. This is the pool water temperature.

Pry off cap

to adjust

Figure 19. Adjustment of Pressure Switch.

THERMOMETER

WITH PETE'S

PLUG

Figure 20. Temperature Rise Measurement

BYPASS

ADJUSTMENT

SCREW