Waterpik Technologies pool/spa heater User Manual

Page 4

Advertising
background image

Page 2

NOTE: See Outdoor Installation section regarding

roof overhang.

These clearances are the minimum acceptable.

Whenever possible, larger clearances should be provided to

assure adequate room for service operations. Note that gas

piping may be provided through either side of the unit. See

later section on gas piping.

Do not install the heater on carpeting or similar

material.

2C-3. Flooring - Typical Installation

The heater must not be installed on combustible

flooring without special measures to assure that the floor

temperatures will not be excessive.

A special base for combustible floors may be

obtained from Waterpik Technologies. The part number

appears in the parts list at the back of this manual (see

Section 5)

In the United States, the National Fuel Gas Code

allows a heater to be placed on a combustible surface when

there is a platform under the heater made of hollow

masonry no less than 4 inches (102 millimeters [mm])

thick, covered with sheet metal at least 24 gauge thick and

extending beyond the full width and depth of the heater by

at least 6 inches (76.2 mm) in all directions. The masonry

must be laid with ends unsealed, and joints matched to

provide free circulation of air from side to side through the

masonry (see Figure 1).

It is best to handle these preparations before the

heater is installed in its final location. Instructions are

provided in subsequent sections of this document.

Contact Waterpik Technologies regarding

installations at elevations above 3,000 feet (980 m). It is

necessary to make changes to the burner tray to assure

proper operation.

2C. Heater Location

2C-1. Installation Information

The LX and LT can be installed outdoors or indoors

as outlined in later sections. In either case location must

be selected with consideration of vent gas exhaust and in

the case of indoor installation, the location must have

suitable provisions for combustion and ventilation air.

Avoid placing the heater in locations where it can

cause damage by water leakage. If this is not possible,

provide a suitable drain pan to catch and divert any

leakage. The pan must not block natural flow of air to or

around the heater.

When a heater or any system component is located

below the pool surface a leak can result in large scale

water loss or flooding. Waterpik Technologies cannot be

responsible for such water loss or flooding. Location of a

heater below or above the pool surface affects operation of

the heater pressure switch. See sections on water piping

and heater start-up for more information about this.

CAUTION

When pool equipment is located below the

pool surface, a leak from any component can

cause large scale water loss or flooding.

Waterpik Technologies cannot be responsible

for such water loss or flooding or resulting

damage.

2C-2. Installation Clearances

Clearances between the heater and combustible

material must be per Table 1.

Figure 1. Non-Combustible Platform.

Notes:

1. Blocks must provide solid base and be braced so they

cannot slip out of place.

2. Air openings in blocks must be arranged to provide

unrestricted opening through entire width or length of

base.

Table 1. Minimum Heater Clearances from

Combustible Surfaces

S i d e o f

H e a te r

A ll In s ta lla ti o n s

U .S . a n d C a n a d a

i n c h

(c m )

B la n k

4

(1 0 .2 )

R e a r

4

(1 0 .2 )

P i p i n g

1 2

(3 0 .5 )

To p

3 9

(9 9 .0 )

F ro n t

1 8

(4 5 .7 )