Table 13, Recommended Minimum AC Wire Sizes (75

°

C)

INVERTER

MODEL

FULL

PASS-THRU

CAPABILITY

FUSE/BREAKER

REQUIRED

CABLE SIZE

REQUIRED

IN CONDUIT

CABLE SIZE

REQUIRED

IN “FREE AIR”*

105-120 VAC

UNITS

60 amps

60 amps

# 6 AWG (THHN)

# 8 AWG (THHN)

220-240 VAC

UNITS

30 amps

30 amps

# 10 AWG (THHN)

# 10 AWG (THHN)

The term "free air" is defined by the NEC as cabling that is not enclosed in conduit or a raceway.
Cables enclosed in raceways or conduits have substantially lower continuous current carrying ability
due to heating factors.

Table 14, Knockout/Hole Size to Conduit Size Required

KNOCKOUT OR HOLE

DIAMETER

TRADE SIZE OF CONDUIT

INCHES

MM

INCHES

7/8 (.875)

22.2

½

1 3/32 (1.093)

27.8

¾

1 23/64 (1.359)

34.5

1

1 23/32 (1.719)

43.7

1 ¼

1 31/32 (1.968)

50.0

1 ½

2 15/32 (2.468)

62.7

2

3

76.2

2 ½

Table 15, Safety Ground Wire Size Table

The ground wire should be sized per NEC 250-95. The following table is derived from this portion of the
NEC code.

Battery DC Disconnect Size

Minimum Size of Copper

Ground Wire

30 Amp or 60 Amp

#10 AWG

100 Amp

#8 AWG

200 Amp

#6 AWG

300+ Amps

#2 AWG or greater