Menu system, Page 54, Battery selling (17) menu heading – Xantrex Technology 120 VAC/60 User Manual

Page 62: Grid usage timer (18) menu heading

Advertising
background image

MENU SYSTEM

Page

54

2001 Xantrex Technology, Inc.

5916 - 195th Street N. E.
Arlington, WA 98223

Telephone: 360/435-8826

Fax: 360/435-2229

www.traceengineering.com

SW Series Inverter/Charger

Part No. 2031-5

Rev. C: February 2001

BATTERY SELLING (17) MENU HEADING

Note: See the battery section of this manual for recommended settings for different battery types.

Set Battery Sell
volts DC

13.4

Set Battery Sell
volts DC

26.8

Set Battery Sell
volts DC

53.6

12 VDC models

Range: 5.0 to 16.0

24 VDC models

Range: 10.0 to 32.0

48 VDC models

Range: 20.0 to 64.0

Sets the level to which the batteries will be discharged when power is being sold from the batteries to the
grid. This is only used if the SELL mode is enabled and the GRID USAGE TIMER (18) is programmed.
This setting will not be adjusted for the battery temperature if the temperature sensor is installed.

Set Max Sell
amps AC

30

Set Max Sell
amps AC

15.0

Set Max Sell
amps AC

35

Set Max Sell
amps AC

16.5

Standard models

Range: 01 to 35

“E” models

Range: 01 to 18

“J & K” models
Range: 01 to 40

“W” models

Range: 01 to 18

Sets the maximum AC amps allowed to be delivered to the utility grid from a solar array and/or the
batteries during utility interactive operation. This is only used if the SELL mode is enabled. If batteries are
being “sold” into the utility grid, this setting together with the SET BATTERY SELL VOLTS DC setting
determines the depth of discharge the batteries will experience. Note: The default setting will vary
between models with different continuous output power ratings.

INFORMATION DISPLAY

The following information is displayed as additional Menu Items.

See menu 9 to enable SELL mode. Make sure LBX is above LBCO volts.

GRID USAGE TIMER (18) MENU HEADING

The Grid Usage Timer selects when power may be drawn from the utility grid for battery charging. It is
used only when either the FLT or SELL modes are selected in the SET GRID USAGE menu item under
the INVERTER SETUP (9) menu heading. Utility Power must be connected to the AC1 for this timer to be
operational.

Start Charge
time

21:00

End Charge
time

21:00

All Models

Range: 00:00 to 23:50

All Models

Range: 00:00 to 23:50

FLT mode: After the START CHARGE TIME, the inverter turns on the battery charger, connects the
utility grid and powers the AC loads from the utility grid and charges the battery to the FLOAT VOLTS DC
setting. At the END CHARGE TIME, the inverter disconnects from the utility grid and powers the loads
from the battery.

SELL mode:

With

the

GRID USAGE TIMER enabled (the START CHARGE TIME is different from the END

CHARGE TIME), the inverter will charge the battery to the FLOAT VOLTS DC setting at the START
CHARGE TIME
. After the END CHARGE TIME, the inverter turns off the battery charger and begins
to “sell” power into the utility grid from the battery (or any other DC sources available and connected to
the batteries) to the SELL VOLTS DC setting. The current will be limited to a maximum level
controlled by the MAX SELL AMPS AC menu item setting under the BATTERY SELLING (17) menu
heading.

With

the

GRID USAGE TIMER disabled (the START CHARGE TIME beginning time is equal to the

END CHARGE TIME), the inverter will use the utility grid (or any other DC sources available and
connected to the batteries) to maintain the batteries to the FLOAT VOLTS DC setting.

In the SELL mode, battery voltage will be held near the SET BULK VOLTS DC setting for the adjustable
ABSORPTION TIME period setting after an AC failure or upon encountering a BULK CHARGE TRIGGER
TIMER
event.