SW Series Inverter/Charger

Part No. 2031-5

Rev. C: February 2001

Set Max Charge
amps AC

20

Set Max Charge
amps AC

30

Set Max Charge
amps AC

15

Set Max Charge
amps AC

35

12 VDC models

Range: 01 to 25

24 VDC & 48 VDC models

Range: 01 to 35

“E & W” models

Range: 01 to 18

“J & K” models
Range: 02 to 40

Sets the maximum amount of AC input current that the battery charger will use to charge the battery. This
can be used to limit the charger output as well. The charger will “back-off” if the combination of AC loads
and the charger reaches the AMPS AC setting of the AC INPUT connected to prevent overloading the
source or tripping breakers. This process occurs automatically.

Set Temp Comp
LEADACID

NICAD

All models

Allows selection of the battery type for the battery temperature compensation system. This effectively
reduces the battery charging set points when the battery is hot and increases them when the battery is
cold. The battery charging set points change

±

0.005 volts per degree Celsius for the LEADACID setting

and

±

0.003 volts per degree Celsius per battery cell for the NICAD setting. These battery setpoint

changes occur if the battery temperature is higher or lower than 25

°

C (77

°

F), and will only occur if the

battery temperature sensor (BTS) is installed. The setting should be changed from the default setting only
if NiCad or Nickel Iron batteries are used.

AC INPUTS (11) MENU HEADINGS

Set Grid (AC1)
amps AC

60

Set Grid (AC1)
amps AC

30.0

Set Grid (AC1)
amps AC

60

Standard models

Range: 00 to 63

“E & W” models

Range: 00 to 31.5

“J & K” models
Range: 00 to 63

This setting determines the level in AC amps at which the inverter begins to back-off the battery charger
or operates in parallel to reduce the load on the utility grid. Typically, this is set to the size of the AC circuit
breaker that feeds the AC HOT IN 1.

Set Gen (AC2)
amps AC

30

Set Gen (AC2)
amps AC

15.0

Set Gen (AC2)
amps AC

30

Standard models

Range: 00 to 63

“E & W” models

Range: 00.0 to 31.5

“J & K” models
Range: 00 to 63

This setting determines the level in AC amps at which the inverter begins to back-off the battery charger or
operates in parallel to reduce the load on the generator. Typically, this is set to the size of the generator’s
circuit breaker feeding the inverter (AC HOT IN 2) or the maximum output amperage ability of the generator.

Set Input Lower
limit VAC

108

Set Input Lower
limit VAC

206

Set Input Lower
limit VAC

88

Set Input Lower
limit VAC

196

Standard models

Range: 80 to 111

“E” models

Range: 170 to 220

“J & K” models

Range: 70 to 90

“W” models

Range: 160 to 210

Sets the lowest voltage at which the inverter is allowed to be connected to the utility grid (AC INPUT 1) or
the generator (AC INPUT 2). When the AC input voltage reaches this level, the inverter will stop battery
charging and begin to invert in parallel with the AC source to reduce the load. If the voltage continues to
drop, the inverter will disconnect and will power the loads from the battery. NOTE: Typically the INPUT
LOWER LIMIT VAC
setting will be based upon the minimum AC voltage tolerable by the AC loads.

Set Input Upper
limit VAC

132

Set Input Upper
limit VAC

254

Set Input Upper
limit VAC

112

Set Input Upper
limit VAC

244

Standard models

Range: 128 to 149

“E” models

Range: 250 to 298

“J & K” models

Range: 105 to 129

“W” models

Range: 240 to 288

Sets the highest voltage at which the inverter is allowed to be connected to the utility grid (AC INPUT 1) or
generator (AC INPUT 2). This is also the maximum voltage at which the inverter will sell power into the line if
SELL is enabled. When this voltage is reached the inverter will disconnect and power the AC loads from the
battery. If this voltage drops below this setting, the inverter will reconnect the loads to the AC source.