SW Series Inverter/Charger

Part No. 2031-5

Rev. C: February 2001

Page

35

SETUP MENU MAP

The SETUP MENU provides all the controls and settings needed when installing or adjusting the
system.
To access the SETUP MENU, press both the red ON/OFF MENU and green GEN MENU buttons
on the Control Panel at the same time. To exit the SETUP MENU, press the red ON/OFF MENU button or
press the down MENU HEADING button until you reach the USER MENU (menu headings 1-8).

Inverter Setup

9

Battery Charging

10

AC Inputs

11

Gen Auto Start
setup

12

Gen starting
details

13

Auxiliary Relays
R9 R10 R11

14

Set Grid Usage
FLT SELL SLT LBX

Set Bulk
volts DC

14.4

Set Grid (AC1)
amps AC

60

Set Load Start
amp AC

20

Set RY7 Function
GlowStop Run

Set Relay 9
volts DC

14.5

Set Low battery
cut out VDC

11.0

Set Absorption
time h:m

02:00

Set Gen (AC2)
amps AC

30

Set Load Start
delay min

5.0

Set Gen warmup
seconds

60

R9 Hysteresis
volts DC

01.0

Set LBCO delay
minutes

10

Set Float
volts DC

13.4

Set Input lower
limit VAC

108

Set Load Stop
delay min

5.0

Set Pre Crank
seconds

10

Set Relay 10
volts DC

14.8

Set Low battery
cut in VDC

13.0

Set Equalize
volts DC

14.4

Set Input upper
limit VAC

132

Set 24 hr start
volts DC

12.3

Set Max Cranking
seconds

10

R10 Hysteresis
volts DC

01.0

Set High battery
cut out VDC

16.0

Set Equalize
time h:m

02:00

Set 2 hr start
volts DC

11.8

Set Post Crank
seconds

30

Set Relay 11
volts DC

15.0

Set search
watts

48

Set Max Charge
amps AC

20

Set 15 min start
volts DC

11.3

R11 Hysteresis
volts DC

01.0

Set search
spacing

59

Set Temp Comp
LeadAcid

NiCad

Read LBCO 30 sec
start VDC

11.0

Close on batt >
setpoint.

Set Exercise
period days

30

Open on batt <
setpoint - Hys

Set Maximum run
time h:m

08:00

Relays have 2
second delay on

Set Max Run time
to 0 to defeat.

Close, 0.1 sec
delay on open

Set Exercise to 0
to defeat.

See menu 9 to
to set LBCO.

Bulk Charge
Trigger Timer

15

Low Battery
Transfer (LBX) 16

Battery Selling

17

Grid Usage Timer

18

Information file
battery

19

End Setup Menu

20

Set Start Bulk
time

00:00

Set Low Battery
TransferVDC

11.3

Set Battery Sell
volts DC

13.4

Start Charge
time

21:00

Batt temp comp
changes battery

To disable timer
set to 00:00

Set Low battery
cut in VDC

13.0

Set Max Sell
amps AC

30

End Charge
time

21:00

voltage reading
away from actual

If grid timer
active set bulk

See menu 9 to
enable LBX mode.

See menu 9 to
enable SELL mode.

After Start
Charge time:

HBCO resets at:
6v/48, 3v/24 and

time after start
charge time.

Make sure LBX is
above LBCO volts.

Make sure LBX is
above LBCO volts.

SELL mode
charges battery.

1.5v/12v under
HBCO.

In SLT mode don’t
disable this

FLT mode
charges battery

LowBattTransfer
used in LBX, FLT

timer. It is the
daily chg time.

After End Charge
time:

Modes only. Goes
back to battery

SELL mode sells
battery to AC1.

at LowBattCutIn
(aka LBCI).

FLT mode drops
AC1 and inverts

For LBX mode set
below LBCI so

Timer on when
start < > end;

charger won’t
cycle batteries

timer off when
start = end

up and down and
set LBCO below.

Sell and float
modes use timer

SLT and LBX mode
ignore timer

MENU HEADINGS