SELLING POWER - FROM A DC CHARGING SOURCE

The simplest and default operation of the SW Series Inverter/Charger in the SELL mode is to “sell” the
excess power from the charging source to the utility when the batteries are full. In this mode, the battery
voltage is held to the regulation level determined by the SET BATTERY SELL VOLTS DC setting. Since
the SET BATTERY SELL VOLTS DC setting is defaulted to the same value as the SET FLOAT VOLTS
DC
setting, the inverter will sell the power from the charging source (wind, hydro or solar, etc.), but will
hold the battery at a charged level.

The regulation process can also be accomplished and allow the three stage charging (float, bulk and
absorption) of the batteries to occur each day by enabling the BULK CHARGE TRIGGER TIMER (15).
The batteries will be maintained at the SET FLOAT VOLTS DC setting until the SET START BULK TIME,
which will charge the batteries near the SET BULK VOLTS DC setting until the end of the ABSORPTION
TIME
.

This operating mode offers the individual system owner with several advantages. The batteries would not
be cycled thereby increasing their life and the batteries would be fully charged in case of a power failure,
resulting in greater system efficiency.

Figure 27, Selling Power From A DC Charging Source; Hypothetical Time Of Day Operational History

Begin Day

00:00

Time

AC amps

20:00

End Day

23:59

DC Volts
13.0

Input
amps AC 00

{

AC amps from grid (+)

{

Set Start Bulk
time 20:00

Set Battery Sell
Volts DC 13.4

Float Volts

DC Setting

Battery Sell Volts

DC Setting

Bulk Volts

DC Setting

Bulk Charge Trigger Timer is

enabled (not the default setting)

Set Bulk Volts
DC 14.4

Charging from the DC

source (wind, hydro or

solar) has started

Absorption Time

Set Absorption
time h:m 02:00

Set Float
Volts DC 13.4

Charging from the DC

source (wind, hydro or

solar) has stopped

Sell to grid period

when the current from

the DC source is greater

than needed to maintain

the Float/Sell Volts DC

setting.

Set Max Sell
amps AC 30

Max Sell Amps

AC Setting

POSITIVE (+) = Inverter is drawing power from grid.
NEGATIVE (-) = Inverter is selling power to grid.