Fig 9 - unit dimensions and clearances – York SUNLINE K4EU120A50A User Manual

Page 10

Advertising
background image

10

Unitary Products Group

550.39-N4YI

FIG 9 - UNIT DIMENSIONS AND CLEARANCES



Overall dimension of the unit will vary if an electric heater, a supply

air plenum or a base is used.

This dimension is required for removal of the DX coil. Only 26" is
required for normal servicing.

!

If the DX coil has to be removed, this dimension is required to
loosen screws that secure the coil to the unit frame. This dimension
will also be required for blower motor access if the piping
connections are made on the opposite side of the unit.

"

Allow enough clearance to trap the condensate drain line.

ACCESSORIES

•ELECTRIC HEATER

Add 15" (381mm) to Unit Height when using 10, 16, 26 or 36kW
Heater

•SUPPLY AIR PLENUM

Add 27" (686mm) to Unit Height when used

•BASE

Add 24" (610mm) to Unit Height when used

MINIMUM CLEARANCES (in./mm)

Side with RETURN AIR opening

- 24 / 610

Side with SUPPLY AIR opening

- 24 / 610



Side with PIPING CONNECTIONS

- 61 / 1549

Side opposite PIPING CONNECTIONS - 26 / 66

!

Bottom

-

"

All dimensions are in millimeters and inches. They are
subject to change without notice. Certified dimensions will
be provided upon request.