KEU090 - SUPPLY AIR BLOWER PERFORMANCE

1

- (CFM)

BLOWER

SPEED

RPM

AIRFLOW

ESP

2

(IWG)

OUTPUT

(BHP)

INPUT

(kW)

ESP

2

(IWG)

OUTPUT

(BHP)

INPUT

(KW)

ESP2

(IWG)

OUTPUT

(BHP)

INPUT

(kW)

ESP

2

(IWG)

OUTPUT

(BHP)

INPUT

(kW)

ESP

2

(IWG)

OUTPUT

(BHP)

INPUT

(kW

2400 CFM

2700 CFM

3000 CFM

3300 CFM

3600CFM

600

0.35

0.62

0.59

0.26

0.70

0.66

0.13

0.78

0.73

-

-

-

-

-

-

655

0.49

0.70

0.66

0.41

0.78

0.72

0.30

0.87

0.82

0.07

0.96

0.90

-

-

-

700

0.60

0.77

0.73

053

0.85

0.80

043

0.95

0.89

0.29

1.06

0.99

0.12

1.17

1.09

800

0.92

0.97

0.90

0.85

1.06

0.99

0.77

1.18

1.10

0.65

1.30

1.21

0.49

1.42

1.32

880

1.18

1.11

1.04

1.11

1.24

1.16

1.03

1.37

1.28

0.91

1.50

1.38

0.77

1.64

1.53

900

1.24

1.15

1.07

1.18

1.28

1.19

1.10

1.42

1.32

0.98

1.55

1.43

0.84-

1.70

1.57

1000

1.58

1.35

1.26

1.53

1.48

1.38

1.46

1.63

1.48

1.37

1.81

1.65

1.24

2.02

1.85

KEU090 - SUPPLY AIR BLOWER PERFORMANCE

1

- (m

3

/s)

BLOWER

SPEED

RPM

AIRFLOW

ESP

2

(Pa)

OUTPUT

(kW)

INPUT

(kW)

ESP

2

(Pa)

OUTPUT

(kW)

INPUT

(kW)

ESP

2

(Pa)

OUTPUT

(kW)

INPUT

(kW)

ESP

2

(Pa)

OUTPUT

(kW)

INPUT

(kW)

ESP

2

(Pa)

OUTPUT

(kW)

INPUT

(kW)

1.1 m

3

/s

1.3 m

3

/s

1.4 m

3

/s

1.6 m

3

/s

1.7 m

3

/s

600

87

0.46

0.59

64

0.52

0.66

32

0.45

0.73

-

-

-

-

-

-

655

122

0.52

0.66

102

0.58

0.72

74

0.65

0.82

17

0.72

0.90

-

-

-

700

149

0.57

0.73

131

0.63

0.80

107

0.71

0.89

72

0.79

0.99

30

0.87

1.09

800

228

0.72

0.90

211

0.79

0.99

191

0.88

1.10

161

0.97

1.21

122

1.06

1.32

880

293

0.83

1.04

275

0.92

1.16

255

1.02

1.28

226

1.12

1.38

191

1.22

1.53

900

308

0.86

1.07

293

0.95

1.19

273

1.06

1.32

243

1.15

1.43

208

1.27

1.57

1000

392

1.01

1.26

379

1.10

1.38

362

1.21

1.48

340

1.35

1.65

308

1.50

1.85

KEU120- SUPPLY AIR BLOWER PERFORMANCE

1

(CFM)

BLOWE

R

SPEED

RPM

AIRFLOW

ESP

2

(IWG)

OUTPUT

(BHP)

INPUT

(kW)

ESP

2

(IWG)

OUTPUT

(BHP)

INPUT

(kW)

ESP

2

(IWG)

OUTPUT

(BHP)

INPUT

(kW)

ESP

2

(IWG)

OUTPUT

(BHP)

INPUT

(kW)

ESP

2

(IWG)

OUTPUT

(BHP)

INPUT

(kW)

3200

3600

4000

4400

4800

700

0.49

1.01

0.94

0.34

1.17

1.09

0.14

1.33

1.24

-

-

-

-

-

-

800

0.84

1.25

1.16

0.71

1.42

1.32

0.53

1.60

1.48

0.30

1.80

1.64

-

-

-

900

1.18

1.48

1.38

1.06

1.70

1.57

0.91

1.92

1.75

0.70

2.18

1.99

0.43

2.45

2.24

950

1.37

1.61

1.50

1.26

1.86

1.71

1.11

2.12

1.95

0.90

2.39

2.18

0.65

2.67

2.44

1000

1.56

1.75

1.62

1.46

2.02

1.85

1.32

2.30

2.10

1.13

2.60

2.38

0.87

2.90

2.65

KEU120 - SUPPPLY AIR BLOWER PERFORMANCE

1

(m

3

/s)

BLOWE

R

SPEED

RPM

AIRFLOW

ESP

2

(Pa)

OUTPUT

(kW)

INPUT

(kW)

ESP

2

(Pa)

OUTPUT

(kW)

INPUT

(kW)

ESP

2

(Pa)

OUTPUT

(kW)

INPUT

(kW)

ESP

2

(Pa)

OUTPUT

(kW)

INPUT

(kW)

ESP

2

(Pa)

OUTPUT

(kW)

INPUT

(kW)

1.5 m

3

/s

1.7m

3

/s

1.9 m

3

/s

2.0 m

3

/s

2.3 m

3

/s

700

122

0.75

0.94

84

0.87

1.09

35

0.99

1.24

-

-

-

-

-

-

800

208

0.93

1.16

176

1.05

1.32

131

1.19

1.48

74

1034

1.64

-

-

-

900

293

1.10

1.38

263

1.27

1.57

226

1.43

1.75

174

1.62

1.99

107

1.83

2.24

950

340

1.20

1.50

312

1.39

1.71

275

1.58

1.95

223

1.78

2.18

161

1.99

2.44

1000

387

1.30

1.62

362

1.50

1.85

327

1.71

2.10

280

1.94

2.38

216

2.16

2.65

1

Unit resistance is based on a wet evaporator coil and clean filters.

2

Available static pressure in IWG (Pa) to overcome the resistance of the duct system and any accessories added to the unit. Refer to Table 6 for the resistance of these

accessories and to Table 7 for additional motor and drive data

NOTE: Motors can be selected to operate into the service factor because they are located in the moving air stream, upstream of any heating device.

LEGEND:

TABLE 4 - BLOWER PERFORMANCE

RPM range for the standard factory-mounted drive com-
ponents.

Exceeds the BHP limitation of the standard
factory-mounted blower motor