York SUNLINE K4EU120A50A User Manual

Page 7

Advertising
background image

3. Using an inclined manometer, determine the pressure drop

across a dry evaporator coil. Since the moisture on an
evaporator coil may vary greatly, measuring the pressure
drop across a wet coil under field conditions would be inac-
curate. To assure a dry coil, the refrigerant system should
be de-energized while the test is being run.

4. Knowing the pressure drop across a dry coil, the actual air-

flow through the unit can be determined from the curve in
Figure 7.

If the airflow is above or below the specified valve, the supply
air motor pulley may have to be readjusted. After one hour of
operation, check the belt and pulleys for tightness and align-
ment.

WARNING: Failure to properly adjust the total system air quan-

tity can result in extensive blower damage.

After readings have been obtained, remove the tubes and seal
up the drilled holes in the side panel with

5

16

" (8mm) dia. dot

plugs (P/N 029-13880) available through normal parts ordering
procedure.

Unitary Products Group

7

550.39-N4YI

TURNS OPEN*

BLOWER DRIVE RANGE (RPM)

KEU090

KEU120

650 -850

700 - 910

5

650

700

4

690

740

3

730

780

2

770

830

1

810

870

0

850

910

* Pulleys can be adjusted in half-turn increments.

TABLE 3 - SUPPLY AIR BLOWER MOTOR PULLEY

ADJUSTMENT

FIG 6 - TYPICAL MOTOR MOUNTING ASSEMBLY

FIG. 7 - PRESSURE DROP ACROSS A DRY

EVAPORATOR COIL VS SUPPLY AIR CFM

FIG. 8 - HOLE LOCATIONS

NOTE: DE-ENERGIZE THE REFRIGERANT SYSTEM BEF-

ORE TAKING ANY TEST MEASUREMENTS TO AS-

SURE A DRY EVAPORATOR COIL.

(PRESSURE DROP READINGS)

DIMENSIONS (in./mm)

A

B

C

D

3 / 76

3 / 76

14 / 356

12 / 305