REFRIGERANT MAINS

Many service problems can be avoided by taking adequate pre-
cautions to provide an internally clean and dry system, and by us-
ing procedures and materials that conform with established
standards.

Hard drawn copper tubing should be used where no apprecia-
ble amount of bending around pipes or other obstructions in
necessary. Use long radius ells wherever possible. If soft cop-
per is used, care should be taken to avoid sharp bends which
may cause a restriction.

Pack fiber glass insulation and a sealing material such as Per-
magum around refrigerant lines where they penetrate a wall to
reduce vibration and to retain some flexibility.

Support all refrigerant lines at minimum intervals (8 ft./2.4m)
with suitable hangers, brackets or clamps.

Braze all copper to copper joints witH Sil-Fos 5 or equivalent
brazing material. Do not use soft solder.
Never braze or solder liquid and suction lines together. The
complete suction line should be insulated with no less the

1

2

"

(12mm) ARMAFLEX or equivalent. If the liquid line is installed
in warm space, it must be insulated.

If it is desirable to tape or wire the liquid and suction lines to-
gether for support purposes, they must be completely insulated
from each other.

INSTALLING REFRIGERANT MAINS

The units are evacuated and dehydrated at the factory and
shipped with a holding charge (1 lb./2.2kg) of Refrigerant-22.
The suction and liquid connections are sealed with copper
disks.

WARNING: Provisions for recovering refrigerant releases

must be available during all phases of installation,

leak testing and charging. Do NOT release refrig-

erant into the atmosphere. A Schrader valve is pro-

vided for refrigerant recovery.

If the unit has already lost its holding charge, it should be leak
tested and the necessary repairs should be made. If the unit
has maintained its holding charge, you can assume that it has
no leaks and proceed with the installation.

Make sure the refrigerant in the lines has been recovered, then
drill a small hole through the discs to prevent any internal pres-
sure from blowing them off and to allow the flow of dry nitrogen
through the connections when unbrazing the closures.

NOTE: To minimize the possibility of system failure due to dirt

and moisture, a filter-drier must be installed in each

liquid line as close to the evaporator as possible.

Filter-driers are not supplied with the evaporator blow-

ers. They are supplied with the matching condensing

sections.

The temperature required to make or break a brazed
joint is sufficiently high to cause oxidation of the copper
unless an inert atmosphere is provide.

CAUTION: Dry nitrogen should flow through a brazed joint at

all times when heat is being applied and until the

joint has cooled.

The liquid, suction and drain connections inside the unit
must be piped to the outside. Refer to Unit Dimensions
for locations and dimensions of these connection.

Unitary Products Group

5

550.39-N4YI

Model

KEU090

KEU120

Evaporator Coil

Rows Deep

3

3

Rows High

27

32

Finned Length (in./mm)

46 / 1168

46 / 1168

Fin/Inch

13

13

Tube O.D. (in./mm)

3

8

/ 9.5

3

8

/ 9.5

Face Area (Ft

.2

/m

2

)

8.6 / 0.80

10.2 / 0.95

Centrifugal Blower

Wheel Dia. x Width

inches

15 x15

15 x 15

mm

381 x 381

381 x 381

Blower Motor*

Nominal Rating (HP/kW)

1

1

2

/ 1.12

2 / 1.5

Filters
(4 Req'd)

Size

inches

16 x 25 x 1

16 x 25 x 1

mm

406 x 635 x 25

406 x 635 x 25

Face Area (Ft.

2

/m

2

)

11.1 / 1.03

11.1 / 1.03

Weight (Lbs,/kg)

Operating

325 / 147

330 / 150

Accessory Weights(Lbs/kg)

Electric Heaters

10 kW

63 / 28.6

63 / 28.6

16kW

66 / 30

66 / 30

26 kW

71 / 32

71 / 32

36 kW

74 / 33.6

74 / 33.6

Supply Air Plenum

102 / 46

102 / 46

Base

60 / 27

60 / 27

Return Air Grille

15 / 6.8

15 / 6.8

Hot Water Coil

105 / 48

117 / 53

*All of these 1450 RPM motors have a solid base, a 56 frame, inherent protection and permanently lubricated ball bearings. Refer to Table 7 for additional motor and drive

data.

NOTE: Refer to the appropriate condensing unit installation instruction for charging data.

Table 2 - PHYSICAL DATA