York SUNLINE K4EU120A50A User Manual

Page 9

Advertising
background image

Unitary Products Group

9

550.39-N4YI

TABLE 5 - ACCESSORY STATIC RESISTANCE (IWG)

ACCESSORY

EXTERNAL STATIC PRESSURE DROP RESISTANCE

IWG/pA

BLOWER CFM/m

3

/s

2400 / 1.1

2700 / 1.3

3000 / 1.4

3300 / 1.6

3600 / 1.7

Electric

Heat

10k W

0.01 / 2.5

0.01 / 2.5

0.01/ 2.5

0.02 / 5.0

0.02/ 5.0

16 kW

0.01 / 2.5

0.02 / 5.0

0.02 / 5.0

0.03 / 7.4

0.04/ 10.0

26 kW

0.03 / 7.4

0.4/ 10.0

0.05 / 12.4 0.06/ 15.0 0.07 / 17.4

36 kW

0.05 / 12.4 0.07 / 17.4 0.08 / 20.0 0.10 / 25.0 0.11 / 27.0

Supply Air Plenum

0.03 / 7.4

0.03 / 7.4

0.04 / 10.0 0.05 / 12.4 0.06 / 15.0

Return Air Grille

0.02 / 5.0

0.03 / 7.4

0.04 / 10.0 0.05 / 12.4 0.06 / 15.0

Add these pressures to the ESP values in the respective blower performance table.

KEU090

KEU120

ACCESSORY

EXTERNAL STATIC PRESSURE DROP RESISTANCE

IWG/pA

BLOWER CFM/m

3

/s

3200 / 1.5

3600 / 1.7

4000 / 1.9

4400 / 2.1

4800 / 2.3

Electric

Heat

10 kW

0.02 / 5.0

0.02 / 5.0

0.03 / 7.4

0.03 / 7.4

0.04 / 10.0

16 kW

0.03 / 7.4

0.04 / 10.0 0.05 / 12.4 0.06 / 15.0 0.07 / 17.4

26 kW

0.06 / 15.0 0.07 / 17.4 0.09 / 22.3 0.11 / 27.0 0.13 / 32.2

36 kW

0.09 / 22.3 0.11 / 27.0 0.14 / 35.0 0.17 / 42.2 0.20 / 50.0

Supply Air Plenum

0.05 / 12.4 0.06 / 15.0 0.07 / 17.4 0.08 / 20.0 0.10 / 25.0

Return Air Grille

0.05 / 12.4 0.06 / 15.0 0.07 / 17.4 0.08 / 20.0 0.10 / 25.0

Add these pressures to the ESP values in the respective blower performance table.

Model

Blower Motor

HP/kW

Power Supply

FLA

Maximum

Fuse Size* Amps

Maximum

Wire Length* * Ft.(m)

KEU090

1

1

2

/1.1

380/415-3-50

3.7

5

650 / 197

KEU120

2 / 1.5

380/415-3-50

4.5

5

500 / 152

* Dual element, time delay fuses.

** Based on three 60° C, 14 AWG, insulated copper conductors in steel conduit and a 3% voltage drop.

TABLE 6 - ELECTRICAL DATA

Advertising