Installation instructions, Site requirements, Flue and chimney requirements – Yeoman EXE MIDI PR1145 User Manual

Page 10: Ventilation, Installation of the gas supply, Location

Advertising
background image

C

A

B

A = 643mm

B = 43mm

C = 12mm

AR0604

1

4.2 This appliance must not be installed in a room that contains

a bath or shower.

4.3 The stove is not suitable for installation against a

combustible wall; all combustible materials must be

removed from the area behind the stove.

4.4 Ensure that all minimum clearances to combustible

materials are complied with (see Diagrams 2 & 3).

AR0522

150

225

150

2

3

50mm

150mm

AR0531

The above dimensions provide adequate clearance to

combustible materials. It may be necessary to add

additional clearance so that the controls can be reached

and spillage tests performed when necessary.

10

INSTALLATION INSTRUCTIONS

SITE REQUIREMENTS

1. FLUE AND CHIMNEY REQUIREMENTS

1.1 The chimney or flue system must comply with the rules in

force, and must be a minimum of 127mm (5") in diameter.

1.2 The minimum effective height of the flue or chimney must

be 3 metres (10ft). Any horizontal flue run from the rear

outlet should not exceed 100mm from the back of the

appliance.

1.3 The chimney or flue must be free from any obstruction. Any

damper plates should be removed or secured in the fully

open position, and no restrictor plates should be fitted.

1.4 The chimney should be swept prior to the installation of the

appliance. However, where it can be seen that the chimney

is clean and unobstructed throughout its entire length, it

need not be swept.

1.5 If the stove is to be fitted into an existing brick built

chimney without a closure plate, a 127mm (5") liner must

be used. Larger lined flues may work, but in some instances

could cause cold start flue problems resulting in nuisance

shutdown. Lined flues above 175mm (7") are not

recommended.

1.6 Due to recent changes to European chimney standards, new

flues and chimneys are now classified by their resistance to

temperature, pressure, corrosion, condensation and fire. To

assist in identifying the correct flue system, the minimum

flue specification is shown in Installation Instructions,

Technical Specification (page 8). Existing chimneys are not

covered by this system.

2. VENTILATION

2.1 Consult the rules in force.

Note: This appliance does not normally require any

additional ventilation when installed in G.B.

3. INSTALLATION OF THE GAS SUPPLY

9.1 Before installation ensure the stove is compatible with the

local gas type and pressure.

9.2 Ensure the gas supply delivers the required amount of gas in

accordance with the rules in force.

9.3 Soft copper tubing and soft soldered joints must be no

closer than 50mm to the base of the burner unit.

9.4 Ensure a means of isolating the gas supply, independent of

the stove's controls

is provided.

9.5 All gas supply pipes must be purged of any debris before

connection to the stove.

4. LOCATION

4.1 This appliance must stand on a non-combustible hearth that

is at least 12mm thick, and projects a minimum of 50mm

from the base of the stove in all directions (see Diagram 1).

Advertising