Installation

42

Powerware

®

Prestige Series Installation and Operator’s Manual for IBM Applications (3000 VA) Uncontrolled Copy

UPS with PPDM Startup

To start up the UPS:

1. If you are connecting the UPS to an AS/400, the QUPSDLYTIM

system value for the UPS Monitoring feature should be set. See
“UPS Monitoring” on page 52 for instructions.

2. Confirm the Bypass switch on the PPDM rear panel is in the

NORMAL position.

3. Steps 4 through 8 are for changing the output voltage. The

output voltage is factory-configured for 230V. If you do not
need to change the output voltage, skip to Step 9.

Use the following table to select the correct output voltage
according to your PPDM.

PPDM Model Number

UPS Voltage Selection*

5-15R PPDM 208: 120/208

208

5-15R PPDM 208: 120/240

208

5-15R PPDM 208: 120

208

5-15R PPDM 240: 120/240

Set to 220V for 110/220V PPDM output
Set to 230V for 115/230V PPDM output
Set to 240V for 120/240V PPDM output

5-15R PPDM 240: 120

Set to 220V for 110V PPDM output
Set to 230V for 115V PPDM output
Set to 240V for 120V PPDM output

5-15R/6-15R PPDM: 208

208

5-15R/6-15R PPDM: 240

240

IEC 320-C13 PPDM

Set to 220V for 220V PPDM output
Set to 230V for 230V PPDM output
Set to 240V for 240V PPDM output

*

The UPS output voltage should be set according to local mains voltage.