Installation

45

Powerware

®

Prestige Series Installation and Operator’s Manual for IBM Applications (3000 VA) Uncontrolled Copy

1. Place the conduit through the access hole on the junction box

(see Figure 10). Connect the exposed conduit wires to the
corresponding compression terminals (see the following table).
Tighten the compression terminals with a screwdriver.

2. Pivot the REPO receptacle guard out of the way, plug the REPO

plug/receptacle UPS connector into the REPO receptacle on the
UPS rear panel and twist the connector in place (see Figure 5
on page 37).

Mounting Holes

Plug/Receptacle
UPS Connector

Three Foot Cord

Terminal Block

Access Hole
for Conduit

Figure 10. Optional REPO Cord Junction Box

Power Cable Terminations

Tightening Torque

Wire Function

Terminal

Position

Terminal Wire

Size Rating*

Entrelec

Phoenix

Contact

REPO

L1

TB1-4

L2

TB1-5

12 - 22 AWG

(4 - 0 mm

2

)

3.5 - 5.3 lb in

5.6 - 6.8 lb in

Ground

TB1-6

(4 - 0 mm

2

)

*

Suggested wire size is #18-AWG (0.75 mm

2

) 75

•C copper wire minimum.

NOTE

The REPO function activates when L1 and L2 are shorted together.