Prestige 3000 UPS Technical Specifications

Input Voltage Range

160 to 276 Vac

Input Power Factor

0.95 Typical

Frequency Range

50/60 Hz ±3 Hz

Surge Protection

IEC 801-4

Output Waveform

Sine wave

Output Voltage
(without PPDM)

200/208/220/230/240 Vac ±3%

Online (BTUs)

978

On Battery (BTUs)

1468

Common Mode Noise
Rejection

>60 dB @ 100 kHz

Transverse Mode Noise
Rejection

>80 dB @ 100 kHz

Input Cord

Detachable 2-meter cord

Outlets (UPS Cabinet)

IEC 320 (1)

Output Voltages and Outlets
(with PPDM)

120/208V: 5-15R (2), 6-15R (2), IEC 320-C19 (1)
120/240V: 5-15R (2), 6-15R (2), IEC 320-C19 (1)

220/230/240V: IEC 320-C13 (6), IEC 320-C19 (1)

120/208V: L6-30R (1), 5-15R (4)
120/240V: L6-30R (1), 5-15R (4)

Batteries (10) per cabinet

12 Vdc, 5 Ah, maintenance-free rechargeable lead acid

Battery Cabinet

120 Vdc

Operating Environment

Temperature: 10

•C to 40•C

(50

•F to 104•F)

Humidity:

5 to 95%
(noncondensing)

Agency Approvals

Safety: EN50091-1

UL 1778
cUL

EMC:

FCC Part 15 Class A
EN50091-2