UPS Operation

53

Powerware

®

Prestige Series Installation and Operator’s Manual for IBM Applications (3000 VA) Uncontrolled Copy

Using the PPDM

The PPDM provides continuous online power for your equipment. With
the PPDM, you can replace or upgrade the UPS without losing power to
your equipment. Figure 16 shows the operation of the UPS with the
PPDM.

UPS

In

Out

UPS Load

PPDM

Battery

Battery

Battery

Utility
Power

Figure 16. UPS and PPDM Block Diagram

Disconnecting the UPS

Use the following procedure to transfer the critical load to Maintenance
Bypass (AC Line operation) and remove the UPS:

1. Turn the Bypass switch on the PPDM to the BYPASS position

(see Figure 17). The PPDM is now powering your equipment
from utility power.

2. Press and hold the Output

Off button until the long beep

ceases (approximately three seconds). The



indicator

remains lit.

3. Remove the Y-cord connections from the UPS rear panel.

C A U T I O N

Do not remove the input power cord or your equipment from the PPDM.