VEGASON 54P … 56P

13

2 Mounting and installation

2.1 Mounting

Version A

Sensors in version A (flange version) are
supplied completely assembled and ready
for operation. Immediately after mounting on
the vessel and electrical connection, they are
ready for operation.

Version B

Sensors in version B are supplied in two
parts (transducer and sensor electronics).
First of all, mount the transducer on the ves-
sel or above the medium. There is a four-pole
jack at the end of the transducer tube. The
respective counterpart to the jack protrudes
out of the lower side of the sensor electron-
ics. Insert the plug of the sensor electronics
(only possible in one position) into the jack of
the transducer tube. Continue pushing the
electronics housing onto the transducer tube,
on which there is a wide and a narrow
groove.

Mounting and installation

The wide groove is used for locking the
headless screws. The narrow groove is an
assembly mark. Move the electronics hous-
ing farther down over the transducer tube
until the mounting groove is no longer visible.
Fasten the housing with the headless screws
to the transducer tube. Use a 5 mm hexagon
screwdriver (or Allen wrench).

Groove for locking the
headless screw

Mounting groove (must
no longer be visible after
mounting)