VEGA VEGASON 54P…56P Profibus PA User Manual

Page 58

Advertising
background image

58

VEGASON 54P … 56P

Technical data

Measuring range
(with sensor version B … D, the transducer end is the reference plane. With sensor version A
the lower side of the flange is the reference plane)

VEGASON 54

1.0 … 25 m (solids 1.0 … 15 m)

VEGASON 55

0.8 … 45 m (solids 0.8 … 30 m)

VEGASON 56

- Version A

1.8 … 70 m (solids 1.8 … 45 m)

- Version B … D

1.4 … 70 m (solids 1.8 … 45 m)

Output signal

digital (Profibus)

the digital output signal (meas. signal) is
modulated onto the power supply and further
processed in the PLC or process control
system.

Integration time

0 … 999 seconds

Measured value display (optional)

Liquid-crystal indication

- in the sensor

scalable output of meas. value as graph and
number value.

- powered externally by the sensor

scalable output of meas. value as graph and

number value. Measured value display can
be mounted up to 25 m away from the sensor.

Adjustment

- adjustment software VEGA Visual Operating on Master-Class 2 PC
- adjustment module MINICOM in the sensor or in external indicating instrument (optional)
- process adjustment interface PACTware

TM

(VVO runs as a subprogram)

- SIMATIC PDM in conjunction with Electronic Device Description (EDD)

Process fitting

VEGASON 54

G 1 A, 1-11.5 NPT, DN 50, DN 80, DN 200

VEGASON 55

G 1 A, 1-11.5 NPT, DN 50, DN 80, DN 250

VEGASON 56

G 1 A, 1-11.5 NPT, DN 50, DN 80, DN 200

Note:
For G 1 A, 1-11.5 NPT, DN 50 and DN 80, an adapter flange is normally required.

Accuracy

1)

(typical values under reference conditions, all statements relate to the nominal measuring
range)

Characteristics

linear

Deviation in characteristics incl.

linearity, reproducibility and
hysteresis (determined acc. to the
limit point method)

< 0.1 %

Linearity

better than 0.05 %

Average temperature coefficient of the

zero signal

0.06 %/10 K

General resolution

max. 1 mm

Resolution of the output signal

0.01 % or 1 mm