VEGASON 54P … 56P

59

Technical data

Characteristics

1)

(typical values under reference conditions, all statements relate to the nominal measuring
range)

Min. span

(between empty and full adjustment)

> 20 mm (recommended > 50 mm)

Ultrasonic frequency (at 20°C)

- VEGASON 54

30 kHz

- VEGASON 55

18 kHz

- VEGASON 56

10 kHz

Intervals

- VEGASON 54

1.0 s

- VEGASON 55

1.5 s

- VEGASON 56

2.0 s

Beam angle at -3 dB emitted power

- VEGASON 54

- VEGASON 55

- VEGASON 56

Influence of the process temperature

negligible, is compensated by a dynamic
temperature detection system integrated in the
transducer. Without temperature compensation,
the ambient temperature error will be 0.18 %/K

Influence of the process pressure

negligible within the approved sensor pressures

Adjustment time

2)

- VEGASON 54

> 2 s (depending on parameter setting)

- VEGASON 55, 56

> 4 s (depending on parameter setting)

Ex technical data

Classification

m (encapsulation of the transducer)

Temperature class (permissible ambient

temperature on the transducer
when used in Ex areas)
- T6

42°C

- T5

58°C

- T4

60°C

- T3

60°C

Ex approved in category or Zone

- VEGASON 56

ATEX

Zone 1 (II 2G)

IEC, CENELEC, PTB

Zone 1

- VEGASON 54 … 56

ATEX

Zone 21/22 (II 2D/3D)

IEC, CENELEC, DMT

Zone 10/11

1)

Similar to DIN 16 086, reference conditions acc. to IEC 770;
temperature 15°C … 35°C; moisture 45 % … 75 %; pressure 860 mbar … 1060 mbar.

2)

The adjustment time is the time required by the sensor to output a correct level (with max. 10 % deviation)
after a sudden level change.