2 status bytes – VEGA VEGASON 54P…56P Profibus PA User Manual

Page 50

Advertising
background image

50

VEGASON 54P … 56P

PA function diagram and parameters

5.2 Status bytes

Coding of the status byte on the PA output value

Status code

Descr. acc. to Profibus standard Probable causes in the VEGA sensor

0x00

bad – non-specific

- Flash-Update active

0x04

bad – configuration error

- Adjustment error
- Configuration error with PV-Scale

(PV-Span too small)

- Differences in meas. unit
- Error in the linearisation table

0x0c

bad – device failure

- Hardware error
- Converter error
- Leakage pulse error
- Trigger error

0x10

bad – sensor failure

- Meas. value error
- Temperature error

0x1f

bad – out of service - constant

- "Out of Service" mode switched on

0x44

uncertain – last unusable value

- Failsafe useable value (Failsafe-Mode =

"Last valid value" and already valid meas.
value since switching on)

0x48

uncertain – substitute set

- Simulation switched on
- Failsafe substitute value (Failsafe-Mode =

"Fsafe value")

0x4c

uncertain – initial value

- Failsafe substitute value (Failsafe-Mode =

"Last valid value" and no valid meas.
value since switching on)

0x51

uncertain – sensor conversion

- Sensor value < lower limit

not accurate – low limited

0x52

uncertain – sensor conversion

- Sensor value > upper limit

not accurate – high limited

0x80

good (non-cascade) - ok

- ok

0x84

good (non-cascade) – active

- Static revision (FB, TB) changed (active

block alarm

for 10 sec., after parameter was written
in static category)

0x89

good (non-cascade) – active

- Lo-Alarm

advisory alarm – low limited

0x8a

good (non-cascade) – active

- Hi-Alarm

advisory alarm – high limited

0x8d

good (non-cascade) – active

- Lo-Lo-Alarm

critical alarm – low limited

0x8c

good (non-cascade) – active

- Hi-Hi-Alarm

critical alarm – high limited

Note:
All 256 possible status byte values can also be generated by simulation. For this reason, the Failsafe-Mode
should be set to "Wrong calculated value", so that the simulated status will not be modified by the Failsafe cal-
culation.