3 parameter listing, Pa function diagram and parameters – VEGA VEGASON 54P…56P Profibus PA User Manual

Page 51

Advertising
background image

VEGASON 54P … 56P

51

PA function diagram and parameters

5.3 Parameter listing

The following parameter listing and function
diagram is used for setup with the automation
system if there is no adjustment software
available. The listing reflects the parameters
of the function block and the transducer
block and should only be used by experi-
enced Profibus technicians. Please make
sure that all VEGA sensors are Profile 3 sen-
sors. As a rule, however, you will carry out
the sensor setup more conveniently with the
VEGA adjustment software VVO or with the
adjustment module MINICOM in the sensor.

The PA parameters and the function diagram
are normally not required for setup and serve
only to deepen the knowledge of the inter-
ested user and enable him to read in the
sensor measured values into the processing
system without an adjustment tool.

Slot Index

Par amet er

Object

Read

Writ e

Type

Size

Reset value

St or e

Unit

Opt ional

manda-

t or y

0

16 Block object

PB

Yes

No

DS- 32

20

C

m

0

17 St rev

PB

Yes

No

Unsigned16

2 0

N

m

0

18 Tag desc

PB

Yes

Yes

Oct et St r ing

32 32 * ' '

S

m

0

19 St r at egy

PB

Yes

Yes

Unsigned16

2 0

S

m

0

20 Aler t key

PB

Yes

Yes

Unsigned8

1 0

S

m

0

21 Tar get mode

PB

Yes

Yes ( *1) Unsigned8

1

S

m

0

22 Mode blk

PB

Yes

No

DS- 37

3

( D)

m

0

23 Alar m sum

PB

Yes

No

DS- 42

8

D

m

0

24 Sof t war e r evision

PB

Yes

No

Oct et St r ing

16

C

m

0

25 Hardware revision

PB

Yes

No

Oct et St r ing

16

C

m

0

26 Device man ID

PB

Yes

No

Unsigned16

2

C

m

0

27 Device ID

PB

Yes

No

Oct et St r ing

16

C

m

0

28 Device ser num

PB

Yes

No

Oct et St r ing

16

C

m

0

29 Diagnosis

PB

Yes

No

Oct et St r ing

4 -

D

m

0

31 Diagnosis mask

PB

Yes

No

Oct et St r ing

4

C

m

0

33 Device cer t if icat ion PB

Yes

No

Oct et St r ing

32

C

o

0

34 Wr it e locking

PB

Yes

Yes

Unsigned16

2 -

N

o

0

35 Fact or y r eset

PB

Yes

Yes

Unsigned16

2 -

S

o

0

36 Decript or

PB

Yes

Yes

Oct et St r ing

32 -

S

o

0

37 Device message

PB

Yes

Yes

Oct et St r ing

32 -

S

o

Advertising