6 configuration – VEGA VEGAMET 515 User Manual

Page 18

Advertising
background image

18

VEGAMET 515

1)

Input5

Input5

Input2

Input4

Input4

Offset cor.
Real value
cor.
Density
cor.
DK-cor.

6 Configuration

6.1 Configuration measurement loop, two independent single measure-

ments

Configuration

The measurement loop configuration is usu-
ally provided as a factory setting. Should a
general modification of the measurement loop
configuration be necessary, first of all a "Re-
set to single measurement“ or "Reset to
linked application“ should be carried out (with
"Reset to single measurement“ the VEGAMET
is prepared for configuration of two inde-
pendent single measurements. With "Reset to
linked application“ it is prepared for configu-
ration of linked applications). Only then can
adjustments in the menu items Application,
Sensor type, Mode and Option be modified.
Proceed in the menu items in the given se-
quence. The adjustment or selection possi-
bilities always depend on what was adjusted
in the previous menu item. When e.g. in the
menu item Application "Level“ is adjusted,
only one sensor type can be selected in the
menu item "Sensor type“ which is suitable for
level detection.

As soon as you have made an adjustment in
the menu item "Option“ and confirmed it, the
display shows the message: "TAG being
created!“.

You choose the application 4/20 mA if you
want to connect a sensor of another manu-
facturer to VEGAMET.

In the following illustrations, different types of
applications are shown. In addition, you will
see which adjustments you have to carry out
in the menu items "Sensor type“ and "Mode“.

The menu item "Position D“ only appears
when in the menu item "Option“ either "Offset
correction“ or "Real value correction“ has
been set. The menu item "Position E“ only
appears when in the menu item "Option“
either "Density correction“ or "DK correction“
has been set.

Confi-
gura-
tion

Config
inputs

Config
meas.
loop

TAG 1
Level

Appli-
cation

Level

Sensor
type

Hydro-
static

Mode

Stan-
dard

Option

no
option

Sensor
coordi-
nation

TAG-
name

TAG -
No. 1

Posi-
tion A

Input
no.1

Fault
signal

on

Param.
TAG-
No. 1

TAG -
No. 1
%

xx,x

off

0/4-20mA
Gauge
Pressure

Capac.
VEGADIF
VEGABAR

Dif-
ference

Tare

Moni-
toring

Input
from

undef-
ined

Input
from

undef-
ined

Posi-
tion D

Input
no.4

Posi-
tionE

Input
no.4

TAG 2
Level

like TAG1

1)

1)

1)

1)

The settings in these menu items can only be
modified if a "Reset to single measurement“ was
carried out beforehand (under menu item "Addi-
tional functions“).