9 simulation, 10 special function: reset, 9 simulation 7.10 special function: reset – VEGA VEGAMET 515 User Manual
Page 47
VEGAMET 515
47
Parameter adjustment
7.9 Simulation
7.10
Special function: Reset
To check the outputs and connected instru-
ments, you can adjust in this menu item any
individual percentage value with the keys [+]
and [–]. The initial point is always the actual
measured value. The indicated value flashes
when the simulation is activated. 15 minutes
after adjustment of the simulated value, the
simulation is automatically terminated and the
display reset to measured value indication.
Param.
TAG-
No. 1
Adjust-
ment
Signal
condit-
ioning
Out-
puts
Simu-
lation
Simu-
lation
%
XX,X
Simu-
lation
Now!
OK?
TAG -
No. 1
%
xx,x
Spe-
cial
funct.
Reset
Level
Reset
OK ?
Reset
Now!
OK ?
Param.
TAG-
No. 1
Adjust-
ment
Signal
condit-
ioning
Out-
puts
Simu-
lation
TAG -
No. 1
%
xx,x
With this reset, all parameter values of the
measurement loop are reset to factory setting
(empty and full adjustment, relay outputs,
current output, volt output and scaling of the
meas. value indication are reset).