6 monitoring – VEGA VEGAMET 515 User Manual

Page 28

Advertising
background image

28

VEGAMET 515

6.6 Monitoring

To activate monitoring, the following
prerequirements must be met:

Meas.
value 50
%

High 5 %

Low –5 %

>55 %

Relay
deenergises

<45%

Configuration

• Choose in the menu item "

Input from

“ (un-

der the menu item "

Monitoring

“) input 4.

• Connect a key switch (opener) to input 4.

Confi-
gura-
tion

Config
inputs

Config
meas.
loop

TAG 1
Level

Appli-
cation

Level

Param.
TAG-
No. 1

TAG -
No. 1
%

xx,x

Moni-
toring

Input
from

Input
no.4

• Choose in the menu range "

Parameter

adjustment relay outputs

“ in the menu item

"

Mode

“ the mode "

Monitoring

“ for the se-

lected relay.

The selected relay activates. By pushing the
key switch (opener opens), the actual meas-
ured value is first of all frozen and, derived
from this, the relay deactivates if this value is
underrun (Low) or exceeded (High). After a
reset and a repeated push of the key switch,
the actual measured value is again frozen.

Param.
TAG-
No. 1

TAG -
No. 1
%
xx,x

Adjust-
ment

Signal
condit-
ioning

Out-
puts

Curr.
out-
puts

Volt
outputs

Relay
outputs

Relay
output1

prop.
to

Per-
cent

Unit

0,0%

Mode

(moni-
toring)

Low

%

5,0

High

%

5,0

Monit.
to

Low &
High

If the monitoring function has to be deacti-
vated, monitoring must first be cancelled in
the menu item "

Mode

“. Then, the allocation of

the correction input (input 4) must be can-
celled under the menu item "

Monitoring

“.

Advertising