3 Environment

Installation in open vessels

In most applications a separate version is recommended
for open vessels, i.e. mounting of the transducer to a
fastening bracket or in another fix position above the
vessel opening.

The max. filling of the vessel depends on the min. distance
of the respective sensor or compact instrument.

Due to variation possibilities of the transducer position, the
requested filling height can be ensured.

Information to socket piece / mounting

-

In case of round top the sensor or the compact
instrument should be mounted on a socket piece
outside the center (mounting on half the range).

-

The emitted sound impulse packets must not be
influenced by the filling stream.

Radius

1

/

2

-

Chamfer the edges of the socket piece.

-

There must be no weldment joints inside the socket
piece.

Min. distance

Min. distance

-

The socket piece must not be flooded by the measured
product.