VEGA VEGAPULS 62 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA_HART four-wire User Manual

Page 36

Advertising
background image

L

iquid

Information:
W

ith VEGAPULS 62 with electronics version "Increased safety",

"

Solid" is preset as factory setting. However, the instrument should be

used preferably in liquids. In such cases, the medium selection should
be set to "Liquid" during setup.

A

ccording to the conductivity and the dielectric value of liquids, the

reflection properties can differ considerably. Therefore additional
options such as "Solvent", "Chem. mixture" and "Water based" are
offered below the menu item Liquid.

W

ith solids, you can also choose between "Powder/Dust", "Granular/

Pellets" or "Ballast/Pebbels".

T

hrough this additional selection, the sensor is adapted perfectly to the

product and measurement reliability, particularly in products with bad
reflective properties, is considerably increased.

E

nter the requested parameter via the appropriate keys, save your

settings and jump to the next menu item with the [->] key.

A

part from the medium, the vessel shape can also influence the

measurement. To adapt the sensor to these measuring conditions, this
menu item offers different options depending on whether liquid or solid
is selected. With "Liquids" these are "Storage tank", "Stilling tube",
"

Open vessel" or "Stirred vessel", with "Solid", "Silo" or "Bunker".

V

essel form

Storage tank

Information:
W

ith VEGAPULS 62 with electronics version "Increased safety",

"

Solid" is preset as factory setting. However, the instrument should be

used preferably in liquids. In such cases, the vessel form should be set
to "Storage tank" during setup.

E

nter the requested parameter via the appropriate keys, save your

settings and jump to the next menu item with the [->] key.

A

linearization is necessary for all vessels in which the vessel volume

does not increase linearly with the level - e. g. with a cylindrical or
spherical tank - and the indication or output of the volume is required.
C

orresponding linearization curves are preprogrammed for these

vessels. They represent the correlation between the level percentage

Vessel form

Linearisation curve

36

VEGAPULS

62 • 4 … 20

mA/HART four-wire

6 S

et up with the indicating and adjustment module PLICSCOM

28440

-EN