3 wiring plan, single chamber housing – VEGA VEGABAR 65 Foundation Fieldbus User Manual

Page 18

Advertising
background image

3

Loop the connection cable through the cable entry on the housing
base

1)

Information:
The cable gland can be mounted in three positions each displaced by
90°. Simply exchange the cable gland against the blind plug in the
suitable thread opening.

4

Connect the wire ends as described under "Single/Double
chamber housing
" according to the numbering

5

Connect the screen to the internal ground terminal, connect the
outer ground terminal above on the housing to potential equal-
isation

6

Tighten the compression nut of the cable entry. The seal ring must
completely encircle the cable

7

Attach the mounting plate again and tighten the screws

The electrical connection of the sensor to the external housing is
hence ready.

5

.3 Wiring plan, single chamber housing

The following illustrations apply to the non-Ex as well as to the Ex-ia
version.

1)

The connection cable is already preconfectioned. If necessary, shorten it to
the requested length, cut the breather capillaries clean. Remove approx.
5 cm of the cable mantle, strip approx. 1 cm insulation from the ends of the
individual wires. After shortening the cable, fasten the type plate with sup-
port back onto the cable.

18

VEGABAR

65 • Foundation Fieldbus

5 Connect to power supply

28260

-EN

-090522