Zero adjustment

000

.0 %

P

=

+0000

.0 mbar

0000.0 mbar

2

Set the requested mbar value with [+] and [->].

3

Confirm with [+] and move to span adjustment with [->].

The zero adjustment is finished.

Information:
The zero adjustment shifts the value of the span adjustment. The span,
i.e. the difference between these values, however, remains un-
changed.

Information:
For an adjustment with pressure, please enter the actual measured
value displayed on the bottom of the display.

If the adjustment ranges are exceeded, the message "Outside
parameter limits
" appears. The editing procedure can be aborted with
[ESC]

or the displayed limit value can be accepted with [OK].

Proceed as follows:

1

Edit the mbar value in the menu item "span" with [OK].

Span adjustment

100

.0 %

P

=

+1000

.0 mbar

0000.0 mbar

Information:
The displayed pressure for 100 % corresponds to the nominal
measuring range of the sensor (in the above example 1 bar =
1000 mbar).

2

Set the requested mbar value with [->] and [OK].

3

Confirm with [OK] and move to the menu overview with [ESC].

The span adjustment is finished.

Information:
For an adjustment with pressure, please enter the actual measured
value displayed on the bottom of the display.

If the adjustment ranges are exceeded, the message "Outside
parameter limits
" appears. The editing procedure can be aborted with
[ESC]

or the displayed limit value can be accepted with [OK].

Carrying out span ad-
justment

38

VEGABAR

65 • Foundation Fieldbus

6 Set up with the indicating and adjustment module PLICSCOM

28260

-EN

-090522

Advertising