VEGA VEGABAR 65 Foundation Fieldbus User Manual

Page 34

Advertising
background image

The adjustment unit is hence switched over from bar to m.

Proceed as follows to select the temperature unit:

4)

à Activate the selection with [OK] and select "Temperature unit

with [->].

à Activate the selection with [OK] and select the requested unit with

[->]

(e.g. °F).

à Confirm with [OK].
The temperature unit is hence switched over from °C to °F.

Proceed as follows:

1

Activate in the menu item "Position correction" the selection with
[OK]

.

Position correction
Offset

P

=
+0000 mbar
53 mbar

2

Select with [->], e.g. to accept actual measured value.

Position correction
Accept current measured

value?

Accept

Edit

3

Confirm with [OK] and move to min.(zero) adjustment with [->].

Proceed as follows:

1

Edit the % value in the menu item "Min. adjustment" with [OK].

Min. adjustment

+000

.0 %

=

+0000

.0 mbar

0000.0 mbar

2

Set the requested percentage value with [+] and [->].

3

Edit the requested mbar value with [OK].

4

Set the requested mbar value with [+] and [->].

5

Confirm with [+] and move to max. adjustment with [->].

The min. adjustment is finished.

Information:
For an adjustment with filling, please enter the actual measured value
displayed on the bottom of the display.

4)

Selection options: °C, °F.

Carry out position cor-
rection

Carrying out min. ad-
justment

34

VEGABAR

65 • Foundation Fieldbus

6 Set up with the indicating and adjustment module PLICSCOM

28260

-EN