VEGA VEGABAR 64 4 … 20 mA_HART User Manual

Page 18

Advertising
background image

2

R

emove the housing socket from the mounting plate

3

2

1

Fig. 7: Components of the external housing for plics

®

devices

1

Screws

2

Wall mounting plate

3

Cable gland

3

L

oop the connection cable through the cable entry on the housing

base

1)

Information:
T

he cable gland can be mounted in three positions each displaced by

90°. S

imply exchange the cable gland against the blind plug in the

suitable thread opening.

4

C

onnect the wire ends as described under "Single/Double

chamber housing" according to the numbering

5

C

onnect the screen to the internal ground terminal, connect the

outer ground terminal above on the housing to potential equal-
isation

6

T

ighten the compression nut of the cable entry. The seal ring must

completely encircle the cable

7

A

ttach the mounting plate again and tighten the screws

T

he electrical connection of the sensor to the external housing is

hence ready.

1)

T

he connection cable is already preconfectioned. If necessary, shorten it to

the requested length, cut the breather capillaries clean. Remove approx.
5

cm of the cable mantle, strip approx. 1 cm insulation from the ends of the

individual wires. After shortening the cable, fasten the type plate with sup-
port back onto the cable.

18

VEGABAR

64 • 4 … 20

mA/HART

5 C

onnecting to power supply

27525

-EN

-081209

Advertising