4 setup procedure – VEGA VEGABAR 64 4 … 20 mA_HART User Manual

Page 32

Advertising
background image

6.4 Setup procedure

I

n HART-Multidrop mode (several sensors on one input) the address

must be set before continuing with the parameter adjustment. You will

nd a detailed description in the operating instructions manual

"Indicating and adjustment module" or in the online help of PACTware
or DTM.

HART

mode

Standard

Address 0

VEGABAR

64

can be used for level as well as for process pressure

measurement. Default setting is level measurement. The mode can be
changed in the adjustment menu.

D

epending on the application only the respective subchapter "Level or

process pressure measurement" is of importance. There, you find the
individual adjustment steps.

Level measurement

S

et up VEGABAR 64 in the following sequence:

1

S

electing adjustment unit/density unit

2

C

arry out position correction

3

C

arrying out min. adjustment

4

C

arrying out max. adjustment

I

n the menu item "Adjustment unit" you select the physical unit in which

the adjustment should be carried out, e.g. mbar, bar, psi…

T

he position correction compensates the influence of the mounting

position or static pressure on the measurement. It does not influence
the adjustment values.

Information:
T

he steps 1, 3 and 4 are not necessary for instruments which are

already preset according to customer specifications!

Y

ou can find the data on the type label on the instrument or in the

menu items of the min./max. adjustment.

T

he indicating and adjustment module enables the adjustmetn without

lling or pressure. Thanks to this, you can carry out your settings

already in the factory without the instrument having to be installed.

T

he actual measured value is also displayed in the menu items for

min./max. adjustment.

I

n this menu item you select the adjustment unit as well as the unit for

the temperature indication in the display.

Address setting HART-
Multidrop

Level or process pres-
sure measurement

Parameter ad-
justment "Level
measurement"

Select unit

32

VEGABAR

64 • 4 … 20

mA/HART

6 S

et up with the indicating and adjustment module PLICSCOM

27525

-EN

-081209

Advertising