2 mounting, 1 mounting instructions, 2 compensation of the atmospheric pressure – VEGA VEGABAR 41 HART User Manual

Page 14: 3 electrical connection, 1 connection instructions, 2 compensation of the atmos- pheric pressure

Advertising
background image

14

VEGABAR 41 (HART

®

)

3 Electrical connection

3.1 Connection instructions

The electronics in VEGABAR 41 requires a
supply voltage of 12 … 36 V DC. It is pro-
vided in two-wire technology, i.e. supply
voltage and current signal are led to the
terminals via the same two-wire connection
cable.

This external energy is provided via a sepa-
rate power supply unit:
- power supply unit, e.g. VEGASTAB 690
- processing unit with integrated DC current

source (e.g. active PLC-input)

- VEGAMET or VEGADIS 371

Make sure that the external energy source is
reliably separated from the mains circuits
acc. to DIN VDE 0106, part 101. The above-
mentioned VEGA instruments meet this re-
quirement, and protection class III is there-
fore ensured.

The external energy source must supply a
terminal voltage of at least 12 V to the trans-
mitter. The actual terminal voltage on the
transmitter depends on the following factors:
- output voltage of the external energy

source under nominal load.

- electrical resistances of the connected

instruments in the circuit (see Connected
instruments, load resistor).

Mounting, Electrical connection

2 Mounting

2.1 Mounting instructions

VEGABAR can be mounted in any position.
Cable entries must point downwards to avoid
moisture ingress. For this purpose the hous-
ing can be rotated by 330° in relation to the
mounting part.

A seal, appropriate for the connection, must
be used for mounting. This seal is either
supplied with VEGABAR or must be provided
by the customer.

2.2 Compensation of the atmos-

pheric pressure

On instruments for gauge pressure meas-
urement, the atmospheric pressure is com-
pensated via a breather facility integrated in
the housing.

Advertising