VEGA VEGABAR 41 HART User Manual

Page 9

Advertising
background image

VEGABAR 41 (HART

®

)

9

Operating conditions

Ambient conditions

Ambient temperature

-40°C … +85°C

- with display module

-20°C … +70°C

Storage and transport temperature

-40°C … +85°C

Product temperature, dependent on
isolating liquid

Temperature
p

abs

>

1 bar

/

p

abs

4)

< 1 bar

- silicone oil

-40°C … +1530°C /

-40°C … +130°C

- silicone oil and cooling element

-40°C … +200°C

/

-40°C … +130°C

- silicone oil and capillaries 1 m

-40°C … +200°C

/

-40°C … +130°C

- vegetable oil

-10°C … +130°C

/

-10°C … +130°C

- vegetable oil and cooling element

-10°C … +200°C

/

-10°C … +130°C

- high temperature oil and cooling elem.

-10°C … +400°C

/

-10°C … +200°C

- high temperature oil and capillaries 1 m -10°C … +400°C

/

-10°C … +200°C

Additional temperature influence of isolating module

Process connection

Temperature coefficient

[mbar/10 K]

FA

Flange DN 25 PN 40 to DIN 2501,
seal surface to DIN 2526 Form D

1.8

FB Flange DN 40 PN 40 to DIN 2501,

seal surface to DIN 2526 Form D

1.0

FC Flange DN 50 PN 40 to DIN 2501,

seal surface to DIN 2526 Form D

2.0

FE Flange DIN 50 PN 40 with extens. 100 mm

1.9

F G Flange DN 50 PN 40 with extens. 200 mm

2.1

FH Flange DN 80 PN 40 to DIN 2501,

seal surface to DIN 2526 Form D

0.4

FK Flange DN 80 PN 40 with extens. 100 mm

0.5

FN Flange DN 1" 300 lbs to ANSI B 16.5,

seal surface RF

1.8

F O Flange DN 2" 600 lbs to ANSI B 16.5,

seal surface RF

2.0

- of cooling elements,

dependent on diaphragm-ø

0.1 … 1.5 mbar/10 K

- of 1 m capillary line

dependent on diaphragm-ø

0.1 … 15 mbar/10 K

Product description

Advertising