VEGA VEGABAR 41 HART User Manual

Page 7

Advertising
background image

VEGABAR 41 (HART

®

)

7

Product description

Electrical data

Adjustment ranges

Zero

adjustable from -20 … +95 % of nominal range

Span

adjustable from 3.3 … 120 % of nominal range

Supply and signal circuit

Supply voltage

12 … 36 V DC

Exd-version

(pressure-tight encapsulation)

18 … 36 V DC

Permissible residual ripple

U

SS

1 V

- at 500 Hz … 10 kHz

U

SS

10 mV

Output signal
- range

3.8 … 20.5 mA

- resolution

6 µA

Current limiting

approx. 22 mA

Fault signal

22 mA (3.6 mA)

Integration time

0 … 10 s adjustable

Rise time

85 ms (ti = 0 sec; 0 – 63 %)

Connection line

2-wire

Max. permissible load

dependent on the supply voltage
(see load diagram)

12

250

0

18

24

30

36

500

750

1000

Load RLtotal in Ohm

Voltage of the external energy U

H

in Volts

1)

Use of a suitable seal for the cable in the PG is necessary for maintaining the housing protection. If the seal
used does not fit the cable, it should be replaced by a suitable one.

Indicating and adjustment current circuit

For connection to

VEGADIS 10 and/or display module

Data transmission

digital

Connection cable

4-wire (standard cable)

Max. line length

25 m

Connection

Cable entry

M20 x 1.5 (for cable-ø 5 … 10 mm)

Screw terminals

for conductor cross-sections of up to 2.5 mm

2

Protective measures

Protection

1)

IP 65

Protection class

III

Overvoltage category

III

Advertising