VEGABAR 41 (HART

®

)

25

Setup

+

{

VEGACONNECT 2

to the sensor

R = 250

On analogue inputs of VEGA signal condi-
tioning instruments or PLC systems, this
resistance is generally > 100

, so that no

damping occurs.

Sensor configuration

Connect the PC via VEGACONNECT 2 di-
rectly to the sensor or to the 4 … 20 mA-
cable. Then start VVO. If the PC was con-
nected with VVO already running, push the
function key

F8

on the PC. Then your monitor

shows this picture "VEGA Visual Operating“.
For configuration of the sensor, first click to

Configuration

, then to

Measuring system

.

In the window "Configuration measuring sys-
tem“ the menu language of VEGABAR can be
adjusted (only on VEGABAR with electronic
version "HL“). As measuring unit you can
choose bar, psi or kPa. By clicking

Reset

the

VEGABAR will be reset to default. Click to

Save

, after you have made modifications.

With

Quit

you return to the window "VEGA

Visual Operating“.

Multidrop operation

VVO supports from version 2.60 the Multid-
rop operation of HART

®

sensors. Multidrop

means that the pressure transmitter always
consumes a supply current of 4 mA, inde-
pendent of the pressure. The output signal is
not transmitted as usual via the current
strength but exclusively via a superimposed
digital signal. By means of this, up to 15
HART

®

sensors can be operated on only one

two-wire cable. Therefore it is necessary to
allocate in advance an address (1 ... 15) to
each individual sensor.

If you want to operate VEGABAR in Multidrop
mode, you have to click to the button

Config-

ure mode

in the window "Configuration meas-

uring system“.

In the following window first choose

Multid-

rop

, then you can adjust the address and

click to

OK

.