VEGA VEGABAR 41 HART User Manual

Page 29

Advertising
background image

VEGABAR 41 (HART

®

)

29

Setup

In the window "Integration time“ you can enter
a time of max. 10 seconds. Then click to

OK

.

Sensor parameter adjustment –
Outputs

Click in the window "Instrument data param-
eter adjustment“ to

Outputs

.

Click in the window "Conditioning“ to

Current

output

.

In the window "Current output“ you can set
the strength of the current in case of failure
(e.g. line break). Furthermore the current can
be inverted, i.e. at 0 % the current output is
20 mA, at 100 % 4 mA. Click to

Save

when

you have modified the adjustment.

Click in the window "Conditioning“ to

Display

of measured value

(only possible if you

have connected a display on VEGABAR).

In the window "Sensor-Display“ you choose
the parameter and the unit which the display
should indicate. If you choose "scaled“, you
can enter the figures corresponding to 0 %
and 100 %. Click to

Save

when you have

finished the adjustments in this window.