The most important adjustment steps – VEGA VEGABAR 41 HART User Manual

Page 33

Advertising
background image

VEGABAR 41 (HART

®

)

33

Setup

The most important adjustment steps

On the following four pages you see a menu
schematic of the HART

®

handheld in conjunc-

tion with VEGABAR process pressure trans-
mitters. The most important adjustment steps
are marked in the menu schematic with the
letters A … E. If you are not familiar with
HART

®

handheld, please note: For the pa-

rameter adjustment, first push the "

ENTER“

key. The adjustment is saved in the hand-
held, but not in the sensor itself.

After you have pushed "

ENTER“, you have to

push "

SEND“ (here in the example for the

min. adjustment).

After pushing "

SEND“, a warning is displayed

that you are about to change device output
and for safety reasons you should switch
your system to manual operation.

Push "

OK“ and the adjustment is now trans-

ferred to the sensor. After a short moment,
you are asked to switch the system from
manual to automatic operation. Confirm with
"

OK“.

You now see the adjustment that was made.

4.2
(5.2)

Generic: SENSOR
PV URV

100.0 mbar

90.3

mbar

HELP DEL

ESC ENTER

Generic: SENSOR

1 PV

LRV bar

2 PV

URV bar

HELP SEND

HOME

Generic: SENSOR

– WARNING –

Pressing "OK“ will
change device output.

Put loop in manual.

ABORT OK

Generic: SENSOR

– WARNING –

Return control loop
to automatic control

OK

Generic: SENSOR

1 PV

LRV bar

2 PV

URV bar

HELP

HOME