industrial areas, screened cable should be used. For HART
multidrop operation we recommend as standard practice the
use of screened cable.

1

2

Fig. 3: Connection of VEGABAR 74
1

Direct connection

2

Connection via VEGABOX 02 or VEGADIS 12

I

f screened cable is necessary, connect the cable screen on

both ends to ground potential. In the VEGABOX 02 or
VEGADIS

12,

the screen must be connected directly to the

internal ground terminal. The ground terminal on the outside of
the housing must be connected to the potential equalisation
(

low impedance).

I

f potential equalisation currents are expected, the connection

on the processing side must be made via a ceramic capacitor
(

e.g. 1 nF, 1500 V). The low frequency potential equalisation

currents are thus suppressed, but the protective effect against

high frequency interference signals remains.

T

ake note of the corresponding installation regulations for Ex

applications. In particular, make sure that no potential equal-
isation currents flow over the cable screen. In case of

grounding on both sides this can be achieved by the use of a
capacitor or a separate potential equalisation.

Cable screening and ground-
ing

Select connection
cable for Ex applica-
tions

14

VEGABAR

74 - 4 … 20

mA/HART

C

onnecting to power supply

28432