3 instrument repair – VEGA VEGABAR 74 4 … 20 mA_HART User Manual
Page 25
à Check the pressure compensation in the housing and
clean the filter element, if necessary
?
4 … 20
mA signal missing
l
W
rong connection to power supply
à Check connection according to chapter "Connection
steps" and if necessary, correct according to chapter
"Wiring plan"
l
N
o voltage supply
à Check cables for breaks; repair if necessary
l
supply voltage too low or load resistance too high
à Check, adapt if necessary
?
C
urrent signal 3.6 mA; 22 mA
l
electronics module or measuring cell defective
à Exchange instrument or return instrument for repair
I
n Ex applications, the regulations for the wiring of intrinsically
safe circuits must be observed.
D
epending on the failure reason and measures taken, the
steps described in chapter "Set up" must be carried out again,
if necessary.
8
.3 Instrument repair
I
f a repair is necessary, please proceed as follows:
Y
ou can download a return form (23 KB) from the Internet on
our homepage www.vega.com under: "Downloads - Forms
and certificates - Repair form".
B
y doing this you help us carry out the repair quickly and
without having to call back for needed information.
l
P
rint and fill out one form per instrument
l
C
lean the instrument and pack it damage-proof
l
A
ttach the completed form and, if need be, also a safety
data sheet outside on the packaging
l
P
lease ask the agency serving you for the address of your
return shipment. You can find the respective agency on our
website www.vega.com under: "Company - VEGA world-
wide"
Reaction after fault rectifica-
tion
VEGABAR
74 - 4 … 20
mA/HART
25
M
aintenance and fault rectification
28432
-
EN
-070718