3 instrument repair – VEGA VEGABAR 74 4 … 20 mA_HART User Manual

Page 25

Advertising
background image

à Check the pressure compensation in the housing and

clean the filter element, if necessary

?

4 … 20

mA signal missing

l

W

rong connection to power supply

à Check connection according to chapter "Connection

steps" and if necessary, correct according to chapter
"Wiring plan"

l

N

o voltage supply

à Check cables for breaks; repair if necessary

l

supply voltage too low or load resistance too high

à Check, adapt if necessary

?

C

urrent signal 3.6 mA; 22 mA

l

electronics module or measuring cell defective

à Exchange instrument or return instrument for repair

I

n Ex applications, the regulations for the wiring of intrinsically

safe circuits must be observed.

D

epending on the failure reason and measures taken, the

steps described in chapter "Set up" must be carried out again,
if necessary.

8

.3 Instrument repair

I

f a repair is necessary, please proceed as follows:

Y

ou can download a return form (23 KB) from the Internet on

our homepage www.vega.com under: "Downloads - Forms
and certificates - Repair form
".

B

y doing this you help us carry out the repair quickly and

without having to call back for needed information.

l

P

rint and fill out one form per instrument

l

C

lean the instrument and pack it damage-proof

l

A

ttach the completed form and, if need be, also a safety

data sheet outside on the packaging

l

P

lease ask the agency serving you for the address of your

return shipment. You can find the respective agency on our

website www.vega.com under: "Company - VEGA world-
wide
"

Reaction after fault rectifica-
tion

VEGABAR

74 - 4 … 20

mA/HART

25

M

aintenance and fault rectification