3 wiring plan – VEGA VEGABAR 74 4 … 20 mA_HART User Manual

Page 16

Advertising
background image

5

.3 Wiring plan

5

1

2

3

4

Fig. 4: Wire assignment, connection cable
1

brown (+): to power supply or to the processing system

2

blue (-): to power supply or to the processing system

3

yellow: is only required with VEGADIS 12, otherwise connect to minus or
with VEGABOX 01 to terminal 3

3

)

4

Screen

5

Breather capillaries with filter element

1

2

+

1

2

3

4

5

6

1

2

3

4

5

6

Fig. 5: Terminal assignment VEGABAR 74
1

To power supply or the processing system

2

Screen

4

)

Wire number

Wire colour/Polarity

VEGABAR 74 terminal

1

brown (+)

1

2

blue (-)

2

3

Y

ellow

2

S

creen

G

round

3)

F

or customer-specific versions already connected with blue (-) when being

shipped.

4)

C

onnect screen to ground terminal. Connect ground terminal on the outside

of the housing as prescribed. The two terminals are galvanically connected.

Direct connection

Connection via VEGABOX 02

16

VEGABAR

74 - 4 … 20

mA/HART

C

onnecting to power supply

28432

-EN