5 Connecting to power supply

VEGAMET 624 • 4 … 20 mA/HART

28969-EN-130701

Before setting up Ex versions, make sure the Ex separating chamber

is plugged on the left housing side (above the sensor terminals). The

pins for type and Ex coding must also be inserted correctly.
Information:

On the active input (terminal 1/2), VEGAMET 624 provides power

for the connected sensors. Power supply and measurement data

are transmitted over the same two-wire cable. This mode is pro-

vided for connection of measuring transducers without separate

operating voltage (sensors in two-wire version).

On the passive input (terminals 3/4), the sensors are not supplied

with energy - only the measured value is transmitted. This input is

for instruments with their own separate operating voltage (sensors

in four-wire version or separators such as VEGATRENN 149). On

a VEGAMET 624 in Ex version, the passive input is not available

due to approval/technical reasons.