6 Setup with the integrated display and adjustment unit

VEGAMET 624 • 4 … 20 mA/HART

28969-EN-130701

English

French

Spanish

Russian

Italian

Dutch

Carry out your settings via the appropriate keys and save with

[OK].

The signal conditioning instrument can be locked with a PIN to protect

the set parameters against unauthorized modification. After activa-

tion, it is not possible to carry out a parameter adjustment via the

built-in display and adjustment unit without entering the previously

specified PIN. This locking does not apply to parameter adjustment

with PACTware and the respective DTM.

With every 4 … 20 mA/HART sensor, the measured value can be

transmitted via analog current signal or digital HART signal. This is

regulated via the HART mode or the address. If a HART sensor is set

to address 0, the sensor is in the standard mode. Here the measured

value is transmitted digitally on the 4 … 20 mA cable.
In mode HART Multidrop, an address from 1 … 15 is assigned to the

sensor. By doing so, the current is fix limited to 4 mA and the meas-

ured value transmission is only made digitally.

First of all, enter the previous address of the sensor to be modified

(factory setting 0), then you can assign the requested HART address

in the range of 01 - 15 in the menu "New address".

With instrument versions with integrated RS232/Ethernet interface,

a manual data transmission to a WEB-VV server can be trigger, for

example, for test purposes. Requirement is that a WEB-VV event was

configured in advance via PACTware/DTM.

In the menu item "Info" the following information is available:

Service - PIN

Service - Sensor address

Service - Data transmis-

sion

Info