3 tendency recognition – VEGA VEGAMET 624 User Manual

Page 39

Advertising
background image

39

8 Application examples

VEGAMET 624 • 4 … 20 mA/HART

28969-EN-130701

When the level was not changed for a longer period, always the same

pump would have been switched on. Via the parameter "Changeover

time", a time can be preset after which a forced changeover of the

pump is carried out. Which pump will be switched on depends ont he

selected pump mode. If all pumps are already switched on, then the

pump still remains switched on. These function can be only adjusted

via PC and DTM.
Note:

If the pump is already switched on when activating the forced

changeover, the timer will not be started. Only after switching off and

on again, will the timer start. If the switch-off delay is set, it will not

be taken into account, i.e. the changeover is carried out exactly after

the preset time for the forced changeover expires. A preset switch-on

delay, however, is taken into account, i.e. the forced changeover to

another pump is carried out after the preset time expires. Before the

newly selected pump switches on, the preset switch-on delay for this

pump must be expired.

8.3 Tendency recognition

The function of the tendency recognition is to recognize a defined

change within a certain time period and to transfer this information to

a relay output.

The information for tendency recognition is generated out of the

measured value change per time unit. The output variable is always

the measured value in percent. The function can be configured for

rising and falling tendency. The actual measured value is determined

and summed with a sample rate of a second. After the max. reac-

tion time, the average value is generated out of this sum. The real

measured value change results then of the newly calculated average

value less the previously calculated average value. If this difference

exceeds the defined percentage value, the tendency recognition

responds and the relay deenergises.
Note:

Activation and configuration of tendency recognition requires PACT-

ware with the suitable DTM. The respective parameters cannot be set

via the integrated display and adjustment unit.

Measured value change higher: Measured value change per

time unit, at which the tendency recognition should respond

Max. reaction time: Time after which a new measured value

generation is carried out and the measured value change is

recalculated

Hysteresis: is automatically always 10 % of the value of "Meas-

ured value change larger than"

Reaction in case of failure: In case of a failure, the relay goes

into the defined condition

Option forced changeo-

ver

Functional principle

Principle of operation

Parameter