6 Setup with the integrated display and adjustment unit

VEGAMET 624 • 4 … 20 mA/HART

28969-EN-130701

– Jump to next higher menu

Note:

Approx. 10 minutes after the last pressing of a key, an automatic reset

to measured value indication is triggered. Any values not confirmed

with [OK] will not be saved.

6.2 Setup steps

Through parameter adjustment, the instrument is adapted to the indi-

vidual application conditions. A measurement loop calibration is the

most important step and should always be carried out. A scaling of

the measured value to the desired physical variable and unit, possibly

including a linearization curve, is often useful. The adaptation of the

relay switching points or the setting of an integration time to smooth

the measured value are further standard adjustment options.
Instruments with Ethernet interface can be provided with a Host name

suitable for the measurement loop. As an alternative to the addressing

via DHCP, it is also possible to adjust an IP address and subnet mask

suitable for your network. If necessary, the e-mail/Web server can be

also configured with PACTware.
Information:

When using PACTware and the corresponding VEGA DTM, additional

settings can be carried out which are not possible or only partly pos-

sible with the integrated display and adjustment unit. When using an

adjustment software, you either need one of the integrated interfaces

(RS232/Ethernet) or the interface converter VEGACONNECT.
Further instructions for setting up the web server and e-mail functions

are stated in the online help of PACTware or the VEGAMET 624 DTMs

as well as the supplementary instructions manual "RS232/Ethernet

connection".

After being switched on, VEGAMET 624 first of all carries out a short

self-check. The following steps are carried out:

Internal check of the electronics

indication of the instrument type, firmware version as well as the

instrument TAG (instrument name)

The output signals jump briefly to the set fault value

Then the current measured values will be displayed and outputted.

The measured value indication displays the digital indication value,

the measurement loop name (measurement loop TAG) and the unit.

An analogue bar graph can also be displayed. By pushing the [>] key,

you move between the individual display options.

By pushing [OK] you move from the measured value indication to

the main menu.

Parameter adjustment

Switch-on phase

Measured value indica-

tion