22

6 Setup with the integrated display and adjustment unit

VEGAMET 624 • 4 … 20 mA/HART

28969-EN-130701

the volume should not be displayed in percent but e.g. in l or kg, a

scaling can be also set.

Enter the requested parameters via the appropriate keys and

save your settings with [OK].

Scaling means converting the measured value into a certain param-

eter and unit. The linearized percentage value is the source signal

which is used as basis for the scaling. The indication can then show

the volume in litres e.g., instead of the percentage value. Indication

values from max. -99999 to +99999 are possible.

Enter the requested parameters via the appropriate keys and

save your settings with [OK].

In this menu item you can enter an unambiguous designation for each

measurement loop, e.g. the measurement loop name or the tank or

product designation. In digital systems and in the documentation

of larger plants, a singular designation should be entered for exact

identification of individual measuring points.

Enter the requested parameters via the appropriate keys and

save your settings with [OK].

Under "Outputs" you will find the relay/current outputs. With relay

output, first of all the requested mode ("Overfill protection" or "Dry

running protection") must be selected.

Overfill protection: Relay is switched off when the max. level is

exceeded (safe currentless condition), relay is switched on again

when the level falls below the min. level (switch-on point < switch-

off point)

Dry run protection: Relay is switched off when the level falls

below the min. level (safe currentless condition), relay is switched

on again when the max. level is exceeded (switch-on point >

switch-off point)

Additional modes such as "Switching window", "Flow" and "Tenden-

cy" can be only adjusted via PACTware and DTM.

Meas. loop - Scaling

Meas. loop - Meas. loop

TAG

Meas. loop - Outputs -

Relays outputs