11 Supplement

VEGAMET 624 • 4 … 20 mA/HART

28969-EN-130701

Relay outputs
Quantity

3 x operating relay, 1 x fail safe relay

Function

Switching relay for level or pulse relay for flow/sampling

pulse

Contact

Floating spdt

Contact material

AgSnO2, hard gold-plated

Switching voltage

min. 10 mV DC, max. 250 V AC/DC

Switching current

min. 10 µA DC, max. 3 A AC, 1 A DC

Breaking capacity

min. 50 mW, max. 750 VA, max. 40 W DC (with U less

than 40 V)

1)

Min. programmable switching hysteresis 0.1 %

Ʋ Fault signal (switch over)

Switching condition off; unchanged

Mode pulse output

Ʋ Pulse length

350 ms

Current outputs
Quantity

3 x outputs

Function

Current output for level or flow/sampling pulse

Range

0/4 … 20 mA, 20 … 0/4 mA

Resolution

1 µA

Max. load

500 Ω

Fault signal (switch over)

0; 3,6; 4; 20; 20.5; 22 mA, unchanged

Accuracy

±20 µA (0.1 % of 20 mA)

Temperature error relating to 20 mA

0.005 %/K

Mode pulse output

Ʋ Voltage pulse

12 V DC at 20 mA with load 600 Ω

Ʋ Pulse length

200 ms

I²C interface for VEGACONNECT
Quantity

1 x on front plate

Plug connection

I²C socket 4-pole for VEGACONNECT

Ethernet interface (optional)
Quantity

1 x, cannot be combined with RS232

Data transmission

10/100 MBit

Plug connection

RJ45

Max. cable length

100 m (3937 in)

RS232 interface (optional)
Quantity

1 x, cannot be combined with Ethernet

Plug connection

RJ45 (modem connection cable on 9-pole D-SUB in the

scope of delivery)

Max. cable length

15 m (590 in)