6 Set up with the display and adjustment module PLICSCOM

VEGASON 63 • 4 … 20 mA/HART - two-wire

28777-EN-130417

– Save value

[->] key to select:

– Menu change

– Select list entry

– Select editing position

[+] key:

– Change value of the parameter

[ESC] key:

– interrupt input

– Jump to next higher menu

The sensor is adjusted via the four keys of the display and adjust-

ment module. The LC display indicates the individual menu items. The

functions of the individual keys are shown in the above illustration.

Approx. 10 minutes after the last pressing of a key, an automatic reset

to measured value indication is triggered. Any values not confirmed

with [OK] will not be saved.

6.4 Setup steps

After VEGASON 63 is connected to voltage supply or after voltage

recurrence, the instrument carries out a self-check for approx. 30

seconds. The following steps are carried out:

Internal check of the electronics

Indication of the instrument type, the firmware as well as the sen-

sor TAGs (sensor designation)

Output signal jumps briefly (approx. 10 seconds) to the set fault

current

Then the actual measured value is displayed and the corresponding

current is transmitted to the cable.

1)

In HART-Multidrop mode (several sensors on one input) the address

must be set before continuing with the parameter adjustment. You

will find a detailed description in the operating instructions manual

"Display and adjustment module" or in the online help of PACTware

or DTM.

HART mode

Standard

Address 0

As VEGASON 63 is a distance measuring instrument, the distance

from the sensor to the product surface is measured. To have the real

product level displayed, an allocation of the measured distance to the

percentage height must be made. To carry out this adjustment, the

distance is entered with full and empty vessel. If these values are not

known, an adjustment with the distance values, e.g. 10 % and 90 %

Adjustment system

Switch-on phase

Address setting HART

multidrop

Parameter adjustment

1)

The values correspond to the actual measured level as well as to the settings

already carried out, e.g. default setting.